REPORTED PROBLEM

POSSIBLE SOLUTIONS

Device will not communicate with the
network controller. (cont.)

• RS485 cable impedance should be matched to

a termination resistor at the end of the cable.

ONICON boards have a jumper selectable 120

ohm resistor for termination. This resistor

should only be used if the display is the last

device on the network cable. (See section

1.5.2 of this manual for details.)

• A unique IP address is required for each

device on TCP/IP networks. Duplicate

addresses will cause multiple devices to

respond to the same poll. This will cause

some or all of the devices on the network to

quit working. (See section 1.6.2 of this manual

for details.)

• Managed IP networks may require that a

gateway IP address be programmed into the

ONICON TCP/IP device. (See section 1.6.3 of

this manual for details.)

Network communications are disrupted when the
device is connected.

• The RS485 network cable connections are

polarity sensitive and must be connected the

same way on every device (i.e. + to + and

- to -). (See section 1.4.1 of this manual for

details.)

• Is the transmit LED flashing? The transmit

LED will only flash when the device is

responding to a poll. A unique address is

required for each device on the network.

Duplicate addresses will cause some or all of

the devices on the network to quit working.

(See section 1.6.1 of this manual for details.)

• A unique IP address is required for each

device on TCP/IP networks. Duplicate

addresses will cause multiple devices to

respond to the same poll. This will cause

some or all of the devices on the network to

quit working. (See section 1.6.2 of this manual

for details.)

• Shield drain connections should be daisy

chained in the same manner as the signal

cables for RS485. The shield drain wire

should be left unterminated at the end of

the cable and connected to earth only at the

network master controller. Shield wires must

not be connected to the RS485 connector on

the System-10.