ONICON System-10 BACnet User Manual

Page 5

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10-BAC Network Interface Installation Guide 04/14 - 0652-8 / 16957

Page 5

1.3 SPECIFICATIONS

BACnet NETWORK INTERFACE

MS/TP RS485

Transceiver:

2-wire, half-duplex

MAC address (device address) range: 1 - 254 (Default: 017)

Device Instance: 0 - 4,194,303 (Default: 57017)

Baud rate:

9600, 19200, 38400, 76800 or Auto-Baud (Default: Auto)

Termination: 120 ohms or none (Default: none)

Biasing:

None

Flow control: None

UDP/IP

Transceiver:

10Base T, 10Mbps, Rj45 connection

Device Instance: 0 - 4,194,303 (Default: 57017)

Default IP address: 192.168.1.24 (Subnet Mask 255.255.255.0) (Port 47808)

Flow control: None

SECTION 1: INTRODUCTION

1.1 PURPOSE OF THIS GUIDE

The purpose of this guide is to provide installation and commissioning procedures and basic

operating and servicing instructions for the ONICON System-10 BTU Meter.

1.2 TYPICAL SYSTEM-10 BTU METER

ONICON’S System-10 is a true heat (Btu) computer which accepts data from several sensors,

performs a series of computations with that data, and displays and/or transmits the results as an

indication of the amount of heat (Btu’s) being transferred per unit time or as a totalized amount.

SYSTEM-10

RETURN

SCROLL

RESET

PROGRAM

BTU METER

ONICON

3864

FLOW DIRECTION

SUPPLY

24 OR 120 VAC

Input Power

Individual Chiller

or Boiler

System

Mains

Local display of flow, temperature and

energy data

RETURN

TEMP

SENSOR

SUPPLY

TEMP

SENSOR

24 VAC INPUT

BACnet

COMMUNICATIONS

TO NETWORK

ONICON insertion

flow meter purchased

separately

Advertising