ONICON System-10 LonWorks User Manual

Page 15

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA • Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]
System-10-LON Network Interface Installation Guide 05/14 - 0654-5 / 16751

Page

15

SECTION 2.0: NETWORK TROUBLESHOOTING TIPS

2.1 TROUBLESHOOTING

REPORTED PROBLEM

POSSIBLE SOLUTIONS

For turbine meters -

No Flow Signal/ Energy Rate

(while hydronic system is

active)

• Verify 24 VDC supply voltage to the flow meter.

• For insertion meters, verify the flow meter is correctly inserted

into the pipe (using depth gage).

• For insertion meters, verify that the flow meter electronics

enclosure is parallel with the pipe.

• Verify correct wiring to the flow meter (see wiring diagram).

• For turbine meters, check turbine(s) for clogging due to debris.

• If none of the above, check hydronic system to ensure that flow is

really present in the line.

• NOTE: Flow meter function cannot be verified by blowing on the

turbine(s). The sensing system requires a conductive liquid to

operate. You can test it by swirling it around in a bucket of water

and looking for the flow indicator LED to flash at the System-10.

Displayed flow rate too high
or too low

• Verify pipe size. Contact ONICON if pipe size is different from

calibration tag.

• For insertion meters, verify that meter is inserted correctly into the

pipe (using depth gage).

• For insertion meters, verify that the flow meter electronics

enclosure is parallel with the pipe.

• For dual turbine meters, confirm that both turbines produce

pulses.

• For turbine meters, check turbine(s) for debris.

• Verify supply voltages (to Btu meter and flow meter).

Displayed temperature(s) too

high or too low vs. expected

values

• Verify wiring to temperature sensor(s), including polarity.

• Verify that thermowells are inserted into the flow stream and

that the temperature sensors are completely inserted into the

thermowells.

Device is not communicating
with the Lon Talk network.

• What is the state of the service pin LED?

• Is it flashing? A flashing service pin LED indicates that the Lon

module has not been commissioned.

• Is it off? A service pin LED that is off indicates that the Lon

module is commissioned and operating normally.

Communications with
the Lon Talk network is
intermittent.

• Is the network properly terminated? The Lon TP/FT bus can be

terminated in 2 different ways.

• A single RC filter can installed at any point on a free topology

network. A dual termination scheme is used with 2 RC filters

installed at the ends of bus networks. Refer to the Appendix A-6

for details.

• What type of cable is used to wire the network? TP/FT networks

should only use twisted shielded pair cable. (Belden 85102 or

equiv.)

For technical assistance, contact ONICON at (727) 447-6140.

Advertising