System-30 BTU Measurement System Manual 05/14 - 0667-2 / 18335

Page 11

3.2.2 Thermowell Installation

IMPORTANT NOTE

It is important that no dirt or other foreign material be allowed into the thermowell as this could

affect the thermal response of the system.

i

Standard Thermowell

The most common installation methods are shown below. Consult ONICON for special
applications.

3.2.3 Temperature Sensor Installation

The temperature sensor is factory matched and permanently attached to the BTU
measurement system. Sensors from different BTU meters cannot be used without being
returned to the factory for recalibration.

Apply a thin coat of thermal compound to the temperature sensor, and gently insert
the temperature sensor all the way into the thermowell until it contacts the bottom of
the cavity. Gently tighten the retainer cap. DO NOT OVERTIGHTEN. The thermowell
completely seals the plumbing system without the retainer cap. The only purpose of the
cap is to keep the sensor from losing contact with the bottom of the thermowell cavity.

IMPORTANT NOTE

Cable length is specified at time of order. This is three wire shielded plenum rated cable. Altering

the cable length will affect calibration. Do not change the cable length without consulting ONICON.