ONICON F-3100 MOD User Manual

Page 8

Advertising
background image

11451 Belcher Road South, Largo, FL 33773 • USA

Tel +1 (727) 447-6140 • Fax (727) 442-5699 • [email protected]

F-3100-MOD Flow Meter Network Interface Installation Guide 05/14 - 0725-1

Page 8

Changing Address, Baud Rate & Parity

STEP

ACTION

COMMENT

0

Obtain the baud rate, parity and device address

settings from the network administrator.

1

The MAIN MENU page shows sub-menu

1-Sensor. Briefly press the right arrow 6 times

to advance to sub-menu 7-Communication.

2

Briefly press the enter key to enter the

7-Communication sub-menu.

The display function shown will be

IF2 prot=.

3

Briefly press the right arrow once to advance to

the address function.

The displayed function shown will be

Address=.

4

Briefly press the enter key once to enter the

address function.

The flashing cursor will move from the

A in adress to the leftmost digit of the

address number.

5

Use the up arrow key to change the value of

the leftmost digit. Once the correct value is

indicated, use the right arrow to move the

cursor to the right. Repeat the process as

necessary until the correct address is entered.

The valid range for the address is from

1 - 247.

6

Briefly press enter once to exit the address

function.

The flashing cursor will move from its

current position to immediately below

the A in address.

To exit the program mode at this point, long press enter twice.
7

Briefly press the right arrow once to advance to

the Baud rate function.

The displayed function shown will be

RS485 bps:

8

Briefly press enter once to enter the Baud rate

function.

The flashing cursor will move from the

R in RS485 to the position right of the

colon.

9

Use the up arrow to change the Baud rate to the

correct setting.

10

Briefly press enter once to exit the Baud rate

function.

The flashing cursor will move from

the position right of the colon to

immediately below the R in RS485.

To exit the program mode at this point, long press enter twice.
11

Briefly press the right arrow 3 times to advance

to the Parity funciton.

The displayed function shown will be

Parity=.

12

Briefly press enter once to enter the parity

function.

The flashing cursor will move from the P

in Parity to the position right of the colon.

13

Use the up arrow to change the parity to the

correct setting.

14

Briefly press enter once to exit the parity

function.

The flashing cursor will move from

the position right of the colon to

immediately below the P in Parity.

15

Long press enter once to return to the MAIN

MENU.

Sub-menu 7-Communication will be

selected.

16

Long press enter once to exit the program mode.

Advertising