Duct Mounted E-BUS CO

2

Sensor Technical Guide

3

Overview

The OE256-07 Duct Mounted E-BUS

CO

2

Sensor with Remote Pickup

Tube

is used for monitoring duct CO

2

levels and is designed for per-

manent mounting in the Return Air duct. It utilizes an aspiration box
to accurately capture CO

2

levels in the duct. It connects to the VCB-X

Controller (OE335-23-VCBX) by using an E-BUS cable with E-BUS
connectors.

See Figure 1 for dimensions.

The Wall Mounted E-BUS CO

2

Sensor (OE256-05) is used for monitor-

ing space CO

2

levels and is designed for permanent wall mounting in

the conditioned space

. It connects to the VCB-X Controller using an

EBC E-BUS Expansion Cable. It can be daisy-chained with the E-BUS
Digital Room Sensor (OE217-02, OE217-03, OE217-04) for applica-
tions requiring both a space CO

2

sensor and space temperature sensor.

For more information, refer to the OE256-05 Wall Mounted CO

2

Sensor

Technical Guide.

Some typical applications are:



Controlling ventilation in a building where the occupancy

varies frequently



Controlling ventilation to ensure excess outdoor air is not

causing energy waste



Ensuring good air distribution throughout building zones

Sensor Overview

Features

The CO

2

Sensor provides the following:



Uses the patented dual beam Non-Dispersive Infrared

(NDIR)

technology



A very accurate and stable sensor guaranteed to maintain

its accuracy due to infrared self-calibration feature of sensor



Sensor accuracy of +/- 50 ppm @ 1000 ppm or 2% of the

measured

value



Annual drift of +/- 2 ppm per year



Measurement range of 0 to 2000 ppm



HB LED under front cover shows active CO

2

sensing

4

3

2

1

3M

E-BUS CONNECTOR
FEMALE END

SENSOR
HOUSING

HINGED
COVER

BRASS
BARB
FITTINGS
FOR
0.170 I.D.
TUBING

BRASS
BARB
FITTINGS
FOR
0.170 I.D.
TUBING

EBC-10F

"WATTMASTER EBUS"

"WATTMASTER EBUS"

EBC-10F

432

1

3M

432

1

3M

120.00” APPROX.

120.00” APPROX.

E-BUS CONNECTOR EXTENSION CABLE WITH MALE ENDS (PROVIDED WITH SENSOR)

0.170 I.D.

TUBING (PROVIDED WITH SENSOR)

FIRE RATED

CO2 PICKUP TUBE (PROVIDED WITH SENSOR)

CO2 SENSOR, HOUSING AND CABLE ASSEMBLY

5.00"

3.31"

4.12"

2.55”

13.00"

APPROX.

8.25"

0.55”

4.06"

2.81”

Figure 1: Duct Mounted E-BUS CO

2

Sensor with

Remote Pickup Tube Dimensions

Environmental Requirements

The Duct Mounted E-BUS CO

2

Sensor needs to be installed in an

environment that can maintain a temperature range between 14°F and
122°F and a humidity range between 5% and 95% RH (non-condensing).