Sensor wiring to vcb-x controller, Duct mounted e-bus co, Sensor technical guide technical guide 6 – Orion System OE256-07 Duct Mounted v.1 User Manual

Page 6: Sensor, Figure 3: duct mounted e-bus co, Sensor is comprised of the co, Vcb-x vcb-x controller

Advertising
background image

Duct Mounted E-BUS CO

2

Sensor Technical Guide

Technical Guide

6

Figure 3: Duct Mounted E-BUS CO

2

Sensor & Digital Room Sensor Wiring for VCB-X Controller

Duct Mounted E-BUS CO

2

Sensor Wiring to VCB-X Controller

Duct Mounted E-BUS CO

2

Sensor

The OE256-07 Duct Mounted E-BUS CO

2

Sensor with Remote Pickup

Tube is used for sensing the current CO

2

level in the HVAC unit’s return

air stream. This is useful when you want an average CO

2

reading in the

area served by the HVAC unit or when you don’t want a wall mounted
E-BUS CO

2

Sensor due to sensor tampering concerns in the space.

The OE256-07 Duct Mounted Return Air CO

2

Sensor is comprised of

the CO

2

Sensor, the WattMaster Aspiration Box Assembly, and a Remote

Pickup Tube. See the dimensional and installation information in Figures
2 & 3
for mounting, wiring, and installation details.

The Duct Mounted Return Air E-BUS CO

2

Sensor with Remote Pickup

Tube is designed to be mounted in the return air duct of the HVAC unit
and uses its integral aspiration box to sample the CO

2

level in the duct.

See Figure 3 below for wiring and installation details.

NOTE:

If using multiple E-BUS Sensors or Modules, the

E-BUS Hub or Adapter Board may be required.

OE256-07 Duct Mounted

E-BUS CO Sensor

2

Note:
1.)
The Duct Mounted E-BUS CO Sensor
Connects To The

Controller Using An

EBC E-BUS Cable Of The Required Length
Or The Provided 10 Foot EBC Cable.

2

VCB-X

VCB-X Controller

MADE IN USA

RELAY CONTACT
RATING IS 1 AMP
MAX @ 24 VAC

RS-485 COMMUNICATION LOOP. WIRE
“R” TO “R”, “T” TO “T” “SHLD” TO “SHLD”

24 VAC POWER

ONLY

WARNING!

POLARITY MUST

BE OBSERVED

OR THE

CONTROLLER

WILL BE

DAMAGED

www.aaon.com

www.orioncontrols.com

VCB-X CONTROLLER

Orion No.:OE335-23-VCBX-A

AAON No.:

V04740

ANALOG INPUTS

AI1 = SPC (SPACE TEMPERATURE SENSOR)

AI2

AI3

AI4

AI5

BI1

BI2

BI3

Bi4

AO1

AO2

AO3

TR1

= SAT (SUPPLY AIR TEMPERATURE SENSOR)
= OAT (OUTDOOR AIR TEMPERATURE SENSOR)
= DCT (DIGITAL COMP. DISCHARGE TEMPERATURE SENSOR)
= SPACE TEMPERATURE SLIDE OFFSET

= EMERGENCY SHUTDOWN
= PROOF OF FLOW
= DIRTY FILTER

= COIL TEMPERATURE SWITCH

= FAN VFD
= ECONOMIZER
= MOD. HEATING

= DIGITAL COMP.

UNLOADER
(24 VAC & UNLOAD

TERMINALS)

BINARY INPUTS

G OUTPUTS

TRIAC OUTPUT

ANALO

STATUS LED BLINK CODES

LED NAME

STATUS1 STATUS2

NORMAL OPERATION

0

1

SAT FAIL

1

2

OAT FAIL

2

2

SPC FAIL

3

2

MISSING EXP MODULE

4

2

CO2 SENSOR FAIL

6

2

AIRFLOW SENSOR FAIL

7

2

MECH COOL FAIL

1

3

MECH HEAT FAIL

2

3

FAN PROOF FAIL

3

3

DIRTY FILTER

4

3

EMERGENCY SHUTDOWN

5

3

LOW SAT

1

4

HIGH SAT

2

4

CONT. TEMP HI ALARM

3

4

CONT. TEMP LO ALARM

4

4

HIGH HEAD PRESSURE

5

4

WATER PROOF FAILURE

6

4

SUCTION PRESSURE ALARM

7

4

LOW LEAVING WATER TEMP

8

4

WattMaster Label

#LB102093-01-A

Rev.: 1B

E-BUS

EXPANSION

E-BUS

EXPANSION

+24

VAC

GND

ALERT LED BLINK CODES BLINKS

NORMAL OPERATION

0

MISSING OR SHORTED
DISCHARGE TEMP. SENSOR

1

IN 30 MIN. CUTOFF PERIOD

3

IN HIGH TEMP. CUTOFF

4

COMPRESSOR LOCKED OUT

6

FAN

RELAY 2

RELAY 3

RELAY 4

RELAY 5

RELAY 6

RELAY
COMMON

10 Foot EBC

E-BUS Cable

(Provided)

EBC E-BUS

Cable

with Jack

Connection

37X04

1.2

1.6

<PC>

4 3 2 1

3M