Remko bl...dc – REMKO BL 262 DC User Manual

Page 42

Advertising
background image

Error E3: Indoor fan speed has been out of control

Shut off the power

supply and turn it on

5 seconds later. Is it

still displaying the

error code?

NO

The unit operates normally.

YES

Shut off the power

sopply, rotate the

cross fan by hand.

Does it rotate prop-

erly?

NO

Disassembly the connection between fan

and motor, check if the bearing is normal?

YES

YES

NO

Check the wires of

fan motor. Are all

the connections

good?

NO

Correct the connec-

tions.

Replace indoor fan

motor.

Replace the

bearing.

YES

Check the resist-

ance value of indoor

fan motor, is it

normal?

NO

Replace indoor fan

motor.

YES

Replace indoor

PCB.

Error E3-E4 and F1-F3 : sensor error

Check the connections between temperature

sensor and PCB. Are the connections good?

NO

Correct the connetions.

YES

Check the resistance of the sensor. Use the

resistance-sensor. Does the Resistance of the

sensor with the value in the table match?

NO

Replace the sensor.

YES

Replace indoor or outdoor PCB.

REMKO BL...DC

42

Advertising
This manual is related to the following products: