REMKO GPM

Electrical connection

The electrical connection of the
unit may only be carried out by
authorised technicians (electrical
power company-approved) in
accordance with the applicable
regulations.
A main/emergency shutoff switch
should be installed in an easily
accessible position on the visible side
of the unit and protected against
unintended actuation. The switch
must disconnect all poles from
the unit with a minimum contact
opening of 3 mm from the mains.

The main/emergency shutoff
switch may only be used in
emergency situations or with
extended periods of non-use.
If it is switched off during
the operation of the unit,
the electrical supply-air fan
cannot cool the combustion
chamber. This can result in
damage to the unit.

ATTENTION

A multipolar isolator with
appropriate electrical
protection must be connected
upstream to the units.
The wire cross-section must
be at least 1.5 mm².

ATTENTION

The units may only be connected
to the mains through outlets/plugs
with reverse polarity protection.
Electrical supply 230/1~/50,
Minimum cross-section of the
mains supply 1.5 mm².

NOTE

Phase and neutral lines may

absolutely not be

interchanged during

connection, because the

flame monitoring device

will otherwise interrupt unit

operation for safety reasons.

Fault F1 is displayed.

NOTE

The use of a multipolar

wire that serves for both

the electronic temperature

regulation and power supply is

not permitted for avoidance of

electromagnetic disturbances.

Rear panel legend:

= Unit power outlet

= Unit plug

= Cable guides

= Unit temperature sensor

Electronic temperature regulation ATR-6 connection to the control PCB

Connect the plug of the electronic temperature regulation to the
customer-installed bus cable, pull out the 2-pole plug connector [CN]
with resistor from the control PCB and re-connect the installed plug with
bus cable.

Electronic temperature

regulation ATR-6

Control PCB

Plug CN

JA

NEIN!

B

L

B = Bus cable

S = live cable

We reserve the right to modify the dimensions and constructional design as part of the ongoing technical development process.