Commissioning

Commissioning should only be

performed and documented by

specially trained personnel.

NOTE

The following steps must be followed
when commissioning:

1. Read this manual carefully before

commissioning.

2. Remember that the resistance of

the connection cable influences
the nominal setting and room
temperature measurement.
For example, a cable with 0.25 mm

2

cross section (telephone wire) and
10m in length causes a nominal
value increase of 2K and a reduction
in room temperature measurement
of 0.01K.

3. Check the resistance at the next

measure point shown.

4. Compare your measurement with

the table given, taking into account
the room temperature.

Test points

Room

temperature in °C

Resistance

in Ohms

+ 10°C

9.950 Ω

+ 15°C

7.855 Ω

+ 20°C

6.245 Ω

+ 25°C

5.000 Ω

+ 30°C

4.028 Ω