RLE LD5000 User Manual

Page 84

Advertising
background image

Appendix A: Modbus Communication

User Guide: LD5000

76 970.484.6510

www.rletech.com

A-6.4 Network Display (Trace)

Type ND<CR> from the RS-232 configuration port to display the RS-485 traffic.



A-6.5 Modbus Display (Trace)

Type MT<CR> from the RS-232 configuration port to display the Modbus packets.


MT
Modbus trace/display is on <press any key to turn
off!>
<LD5000>
ins: 02 04 00 00 00 03 B0 38
mbreg matches: 3
Outs: 02 04 06 00 00 00 00 00 01 B5 A3
ins: 02 04 00 00 00 03 B0 38
mbreg matches: 3
Outs: 02 04 06 00 00 00 00 00 01 B5 A3
ins: 02 04 00 00 00 03 B0 38
mbreg matches: 3
Outs: 02 04 06 00 00 00 00 00 01 B5 A3
ins: 02 04 00 00 00 03 B0 38
mbreg matches: 3
Outs: 02 04 06 00 00 00 00 00 01 B5 A3
ins: 02 04 00 00 00 03 B0 38
mbreg matches: 3
Outs: 02 04 06 00 00 00 00 00 01 B5 A3

ND
ok
RS485 Monitor On <press any key to turn off!>
<LD5000>
{02}{04}{00}{00}{00}{03}{B0}{38}Modbus wakeup
{A3}{02}{04}{00}{00}{00}{03}{B0}{38}Modbus wakeup
{A3}{02}{04}{00}{00}{00}{03}{B0}{38}Modbus wakeup
{A3}{02}{04}{00}{00}{00}{03}{B0}{38}Modbus wakeup
{A3}{02}{04}{00}{00}{00}{03}{B0}{38}Modbus wakeup
{A3}{02}{04}{00}{00}{00}{03}{B0}{38}Modbus wakeup
{A3}{02}{04}{00}{00}{00}{03}{B0}{38}Modbus wakeup
{A3}{02}{04}{00}{00}{00}{03}{B0}{38}Modbus wakeup
{A3}