RLE SeaHawk Sensing Cable Installation User Manual

Page 2

Advertising
background image

Install SeaHawk Sensing Cable on Pipes

Since SeaHawk sensing cable is very flexible, it can be installed around pipes. This can help pinpoint leaks in a wide variety of

applications. Verify whether your pipe installation is horizontal or vertical. Cable is installed differently in each application.

If sensing cable is installed on horizontal pipes:

• Run the cable along the bottom of the pipe and secure it with cable ties or tape every two to three feet (0.6 to 0.9m).

If sensing cable is installed on vertical pipes:

• Wrap the cable around the pipe at a 30 - 45 degree angle, repeating the angle at appropriate spacing as you move down

the pipe. Use cable ties every 3 to 5 feet (0.9 to 1.5m) to secure the cable to the pipe.

If the sensing cable is installed on chilled water lines, wrap the pipes with insulation after installing the cable. This helps control

condensation, which can trigger alarms.

SeaHawk Sensing Cable FAQ

Question

Response

How do I secure sensing

cable to the floor?

RLE recommends the use of J-clips. J-clips are nylon cable clips with a self-adhesive backing.

J-clips hold sensing cable securely in place without pinching or binding the cable, which can cause

false alarms.

J-Clips should be placed 5 to 6 feet apart throughout an installation, and 3 feet apart when cable is

routed in front of CRAC units. Because the J-clip’s adhesive backing does not work well on porous

concrete floors, apply a drop of silicone or another nonconductive adhesive to help secure the

J-Clip to the floor.

My water leak detection

cable touches metal. Is

this a problem or potential

problem?

In general, no. The two water sensing wires are covered by a nonconductive polymer weave. This

weave isolates the cable from metal surfaces. However, as with all electrical wires and cable, avoid

sharp objects that can slice or pierce through the insulation and nonconductive polymer weave.

The sensing cable is routed

so that it has to cross over

itself. Can this cause false

alarms?

Crossing sensing cables will not cause false alarms, but it can cause a false distance reading if a

leak occurs at the crossover point. If the cables must cross, use a 10 foot section of non-sensing

cable to jump over the section of sensing cable.

If I suspect a bad section

of sensing cable, how can

I verify that it is ok without

sending it back to RLE for

warranty evaluation?

It can be very difficult to remove sensing cable, so verify the cable is working before you attempt

to remove it and return it to the manufacturer. Use either a cable tester (RLE part # LDCE) or

request a Cable Break Alarm assessment document from RLE to determine which section of cable

may be faulty.

My system shows an alarm

condition, but a leak is not

found at location shown

on display. The system will

not clear. It is in alarm all

the time!

The most common causes for this condition includes:

1. Water is touching the cable in two places at the same time. The distance reading is an

average of the two values. For example, if leaks are detected at 200 feet and at 100 feet, the

system would register a leak at 150 feet ( (200 + 100)/2 = 150 ). This is a common problem

when, after an alarm sounds, the operator resets the system without recording the first value

displayed. It is very rare that water will touch two places on the same cable at the exact same

time. This situation is true for all systems which measure distance. Check the Alarm History

log for the first incidence of the leak.

2. The cable has been exposed to high humidity, or the dew point has been reached. This is

especially common when two or more air conditioners share the same under-floor space.

Problems of this nature can be resolved as follows:

a. Fix the air conditioners. This is sometimes easier said than done as most people believe if

the unit is on and cooling, it is working properly. Extensive investigation may have to be

done just to prove the air conditioner is faulty.

b. Turn the sensitivity adjustment on the controller to its least sensitive setting. This should

keep the system from alarming, but will not resolve the air conditioner problem.

c. Move the cable at least 10’ away from the front of the air conditioner.

d. Cover the sensing cable in front of the air conditioner with spiral wrap (plastic covering

which allows water in but keeps dew point from condensing water on the cable).

3. A cable has been contaminated either chemically (floor sealing chemicals dissolve and damage

cable), or physically (small metallic chips from filings or solder around pipes or wires from

electrical installation). This requires replacement of the cable.

4. The cable has become damaged - most often from a floor tile being dropped on it. Damaged

cable must be repaired or replaced.