SYMPTOM

POSSIBLE CAUSE

PROBABLE FIX

Ice is made, but will not harvest

Will not harvest due to hot gas
valve not opening.

Check for voltage to coil in
harvest, if there is voltage
replace hot gas valve

Slow/incomplete harvest due to
hot gas valve not fully open.

Check low side pressure in
harvest, replace hot gas valve if
too low with correct ref. charge.

Makes ice, but very little

High discharge pressure, due to
dirty condenser; faulty fan motor;
not enough water thru water
cooled condenser, high water
temperatures, water reg. valve set
too high.

Check for causes of high
discharge pressure and correct.

Inlet water temperatures and
room ambient very high

Advise user, suggest additional
room cooling.

Long freeze cycle due to hot gas
valve leaking thru.

Check temperature of tubes to
and from hot gas valve; there
should be a temperature drop
across the valve in the freeze
cycle. Replace valve if temps are
nearly equal.

Compressor inefficient

Check/replace compressor

Cubes are wrong size/shape

Ice size thermostat not adjusted
properly

Adjust ice size thermostat; use
gauge shipped with machine

Freeze cycle too short due to
heater open

Check/replace heater on ice size
thermostat probe tube.

Water system is restricted with
minerals

Clean water system with
Scotsman Ice Machine Cleaner

Ice thickness probe tube covered
with minerals

Clean tube with ice machine
cleaner

Not enough water

Check water supply pressure

Check water supply for restrictions

Too much superheat

Check superheat, replace TXV if
too high.

Check hot gas valve for leak-thru;
replace if leaks thru.

Ice fused together in bin

Ice in bin too long

Advise user to pour water on ice
to ease removal

Too many minerals in water

Suggest water treatment to user.