SL Power Electronics GLD140 User Manual

Gld140 series installation instructions

Advertising
background image

DC POWER SUPPLIES INC.
2311 Statham Pkwy
Oxnard, CA 93033 + 805-486-4565
www.condorpower.com

MODEL NUMBERS: GLD140X-C or -CF where X equals any alpha character A through Z, -C is a slotted cover option
and –CF is a solid cover with fan option. Models may be followed by suffix –XXX and/or G, where XXX may be any
number from 001 thru 999. The –XXX suffix are used for value added configurations that have no impact on safety and
suffix G indicates compliance to RoHS.

RATINGS:

Input: 100-240 V ac, 3.0 A, 50/60 Hz
Output:

Max Output Power at ambient of 50°C:

180 Watts maximum with cover/fan option or slotted cover with a minimum of 150 LFM airflow.

140 Watts maximum with no airflow and no cover.

Max Output Current in table below is with Convection / 150 LFM airflow cooling except GLD140H which is convection

only.

Output #1

Note 2

Output #2

Output #3

Output #4

Model

Volts

Current

Volts

Current

Volts

Current

Volts

Current

GLD140A

5

16 / 20 A

12

6 / 8 A

12

4 / 5 A

-12

0.75 / 1.2 A

GLD140B

5

16 / 20 A

12

6 / 8 A

5

4 / 5 A

-12

0.75 / 1.2 A

GLD140C

5

16 / 20 A

12

6 / 8 A

15

4 / 5 A

-15

0.75 / 1.2 A

GLD140D

5

16 / 20 A

24

4 / 6 A

12

4 / 5 A

-12

0.75 / 1.2 A

GLD140E

5

16 / 20 A

24

4 / 6 A

15

4 / 5 A

-15

0.75 / 1.2 A

GLD140F

5

16 / 20 A

15

5 / 7 A

12

4 / 5 A

-12

0.75 / 1.2 A

GLD140G

5

16 / 20 A

3.3

10 / 12 A

12

4 / 5 A

-12

0.75 / 1.2 A

GLD140H

5

6 A

12

2.5 A

15

2 A

-15

2 A


Notes:
1. For all models, fan output is 12 V dc, 0.25 A max.
2. Minimum output current of 3 A is required on output #1 for proper regulation.
3. Maximum Operating Relative Humidity 96 %, no condensation.
4. Storage: -40 to +85 °C. Units should be allowed to warm-up under non-condensing conditions before application of

power.

CERTIFICATION: All models are Certified to be in compliance with the applicable requirements of UL 60601-1, CSA
22.2 No. 601.1, EN 60601-1, and IEC 60601-1.

CLASSIFICATION

:

(5.1) Protection against electric shock = Class I

(In accordance with sub-

clause 5 of IEC 60601-1)

(5.2) Degree of protection against electric shock = Not acceptable for applied part without
additional isolation (contact factory for details)

(5.3) Protection against harmful ingress of water = Ordinary (no protection)

(5.5) Have not been evaluated for use in the presence of a flammable anaesthetic mixture with
air, oxygen, or nitrous oxide. This evaluation is to be made on the end equipment by the OEM.

(5.6) Mode of operation = Continuous

SAFETY DECLARATION: Condor DC Power Supplies, Inc. declares under our sole responsibility that all
models listed above are in conformity with the applicable requirements of EN 60950-1 following the provisions
of the Low Voltage Directive 73/23/EEC.

GROUNDING: Protection Class I requires that the ground terminal be bonded to Protective Earth in the end application.
Using this terminal for the primary system earthing terminal is not recommended.

OUTPUTS: It is recommended that the output common or return be connected to Protective Earth in the end application.
The output is not acceptable for patient connection without additional isolation. The DC output is SELV under normal and
single fault conditions. Output #3 is isolated from Ground and may be referenced positive or negative.

41-34338-0001 Rev. G 11/30/05

Page 1 of 2

GLD140 SERIES

INSTALLATION INSTRUCTIONS

Advertising