SL Power Electronics GLM50 Single O/P User Manual

SL Power Electronics Equipment

Advertising
background image




SL Power Electronics, Corp..
6050 King Dr. Bldg. A
VENTURA, CA 93003 + 805-486-4565

MODEL NUMBERS: GLC50-X-YYYG, where X represents the output voltage which may be any number from 3.3 thru
48, -YYY represents Value Added Options not related to Safety and G represents compliance to RoHS. Model may be
followed by suffix –C for chassis & cover option.

R A T I N G S

Input: 100-240 VAC, 1.4 A, 50/60 Hz
Output:

Model

Watts

1

Output

Model

Watts

1

Output

GLM50-3.3

26.4

+3.3VDC 8A

GLM50-15

50

+15VDC 3.3A

GLM50-5

40

+5.1VDC 8A

GLM50-24

50

+24VDC 2.1A

GLM50-12

50

+12VDC 4.2A

GLM50-28

50

+28VDC 1.8A

Notes:
1. -C option requires 24 cfm minimum airflow for full rated output power.
2. Maximum operating ambient is 50°C.
3. Maximum Relative Humidity 96%, no condensation.

CERTIFICATION: All models are Certified to be in compliance with the applicable requirements of
UL/CSA/EN/IEC 60601-1.

CLASSIFICATION:

(5.1) Protection against electric shock = Class I

(In accordance with sub-

(5.2) Degree of protection against electric shock = Signal output or intermediate

clause 5 of IEC 601-1)

(5.3) Protection against harmful ingress of water = Ordinary (no protection)

(5.5) Have not been evaluated for use in the presence of a flammable anaesthetic

mixture with air, oxygen, or nitrous oxide. This evaluation is to be made
on the end equipment by the OEM.

(5.6) Mode of operation = Continuous

SAFETY DECLARATION:

SL Power Electronics Corp (SLPE). declares under our sole responsibility

that all models listed above are in conformity with the applicable requirements of EN60950 following the
provisions of the Low Voltage Directive 2006/95/EC.

GROUNDING: The Protective Earth (ground) terminal must be bonded to Protective Earth

in the host equipment. Using the Protective Earth terminal on the supply for grounding the host
equipment is not recommended. A separate dedicated grounding point should be used.

OUTPUTS: Output common should be connected to Protective Earth in the end application. The
output is intended for Protectively Earthed Signal Output and Intermediate Circuits only. The output is
not acceptable for patient connection without additional isolation. The DC output is SELV under normal
and single fault conditions.

OVERVOLTAGE PROTECTION: The output is monitored for an overvoltage condition. In some
applications where an overvoltage condition could result in a hazard as defined in applicable safety
standards, redundant or additional overvoltage protection may be required. Consult factory for details.

CAUTION: When performing Dielectric Strength Tests, catastrophic failure of the unit may result if a
Dielectric Strength test voltage greater than 1800 V ac is applied between primary and secondary
circuits. The components providing isolation from primary to secondary cannot be tested while installed
in the power supply without overstressing basic (primary to ground) insulation. All isolating
components are individually 100 % tested at 4800 V ac prior to installation.

41-34648-0001 Rev. E 3/28/08

Page 1 of 2

INSTALLATION INSTRUCTIONS

GLM50 SINGLE OUTPUT SERIES

Advertising