ISOLATION: The creepage distance between primary and ground is 4 mm minimum; between primary
and secondary circuits is 8 mm minimum. Secondary to ground creepage is not defined or controlled.
The output common is bypassed to ground using a 2200 pF 1 kV capacitor. The required creepage and
clearance distances from primary circuits to ground and secondary circuits must be maintained after
installation to preserve the intended safety.

TEMPERATURES: The maximum operating temperatures of certain safety components, as defined in
the applicable safety standards, must not be exceeded after installation to preserve the intended safety.
The output power, ambient air temperature and the availability, amount, direction and/or restriction of
airflow influence the temperatures of these components.

OVERCURRENT PROTECTION: The internal fuse is located in the phase lead only. EN 60601-1
requires that both supply leads (phase and neutral) be protected against overcurrent. Complete
overcurrent protection must be provided in the host equipment. Fuse ratings must not exceed that
specified for the internal fuse, must meet the requirements of EN 60601-1, and be acceptable for the
country in which the host equipment is to be installed.

WARNING! RISK OF FIRE! A blown internal fuse is an indication of catastrophic failure of circuit
component(s). Refer to fuse marking on the supply for rating. Repair must be performed by SLPE
authorized personnel.

WARNING! SHOCK HAZARD! Dangerous voltages are present on some components, printed wiring
traces and heatsinks.

Attention, Consult
Accompanying Documents

Alternating Current

Attention, Dangerous Voltages

Earth (Ground)

EXPLANATION OF SYMBOLS

Direct Current

C O N N E C T I O N S

J1 Pin

AC Input

J2 Pin

DC Output

1

Line

1

Output #1 (+)

3

Neutral

2

Output #1 (+)

3

Output #1 (+)

4

Return

5

Return

6

Return

RECOMMENDED MATING CONNECTORS

J1 Amp Housing 640250-3 Contact 770522

CAUTION

J2 Amp Housing 640250-6 Contact 770522

Do not exceed 5 Amps per contact.

SLPE. will not be liable for the safety, reliability or performance of these power supplies if a) any changes, modifications or repairs are carried out by other than authorized agents of
SLPE., or b) the installation of the supply is not in accordance with these installation instructions and the applicable UL, CSA, and EN/IEC safety standards.

41-34648-0001 Rev. E 3/28/08