ISOLATION: The creepage distance between primary and ground is 4 mm minimum; between primary and secondary

circuits is 8 mm minimum. Secondary to ground creepage is not defined or controlled. The output common is bypassed to

ground using a 1 kV capacitor. The required creepage and clearance distances from primary circuits to ground and secondary

circuits must be maintained after installation to preserve the intended safety.
TEMPERATURES: The maximum operating temperatures of certain safety components, as defined in the applicable safety

standards, must not be exceeded after installation to preserve the intended safety. The output power, ambient air temperature

and the availability, amount, direction and/or restriction of airflow influence the temperatures of these components.
OVERCURRENT PROTECTION: The internal fuse is located in the phase lead only. EN 60601-1 requires that both

supply leads (phase and neutral) be protected against overcurrent. Complete overcurrent protection must be provided in the

host equipment. Fuse ratings must not exceed that specified for the internal fuse, must meet the requirements of EN 60601-1

and be acceptable for the country in which the host equipment is to be installed.
WARNING! RISK OF FIRE! A blown internal fuse is an indication of catastrophic failure of circuit component(s). Repair

must be performed by Condor authorized personnel. Refer to fuse marking on the supply for rating.
WARNING! SHOCK HAZARD! Dangerous voltages are present on some components, printed wiring traces and heatsinks.

Attention, Consult

Accompanying Documents

Alternating Current

Attention, Dangerous Voltages

Protective Earth (Ground)

EXPLANATION OF SYMBOLS

C O N N E C T I O N S

J1

TB1

AC INPUT

J2

J3

TB2

DC OUTPUTS

1

1 Line

1 Power Fail

1,2,3,4,13,14,15,16 1,2,7,8

+ Output

3

2 Neutral

2 - Sense

5,6,7,8,9,10,11,12

3,4,5,6

Return

5

3 Ground

3 + Sense

4 N/C

MATING CONNECTORS: J1 Amp Housing 640250-5 Contact 770522-1

J2 Amp 640440-4

J3 Amp Housing 1-640250-6 Contact 770522-1

CAUTION: Do not exceed 4 A per pin on J3 or 15 A per terminal on TB2.

Condor DC Power Supplies Inc. will not be liable for the safety, reliability or performance of these power supplies if a) any changes,

modifications or repairs are carried out by other than authorized agents of Condor DC Power Supplies Inc., or b) the installation of the

supply is not in accordance with these installation instructions and the applicable UL, CSA, and IEC/EN safety standards.

41-33340-0001 Rev. E 09/02/04