02 ratings, Ratings, Title: southern states – csv – Southern States CSV User Manual

Page 3

Advertising
background image

Title: Southern States

– CSV

Vertical Interrupter Style Circuit Switcher

Product Specification Guide

Page 3 of 9

Publication No.: PSG-806-CSV 06012011

3.02 Ratings

3.02.01 Electrical

Maximum kV Rating

27

38

38

48.3

72.5

38

48.3

72.5

BIL (kV)

150

200

200

250

350

200

250

350

Continuous Current

Primary Fault

Interrupting

Secondary Thru-Fault

Interrupting

Interrupting Time

Power Frequency

Short-Time Withstand

Peak Withstand

Short-Circuit Making

Insulator Design

Ambient Temperature
Range

-40º C to +50º C

1200 A

25 kA

5 cycles

-40º C to +50º C standard

(-50º C to +50º C optional)

Porcelain

Composite

Porcelain

3 cycles

40 kA

1200 A, 1600 A, 2000 A, 2500 A

4

Ratings

62.5 kA

25 kA

50/60 Hz

1200 A & 1600 A

25 kA

5 cycles

50/60 Hz

25 kA (3 sec)

4

-30º C to +50º C

40 kA

104 kA

40 kA (3 sec)

4

60 Hz

40 kA (3 sec)

104 kA

40 kA (3 sec)

Maximum kV Rating

48.3

72.5

123

145

170

Interrupter/Blade BIL (kV)

250

350

550

650

750

Continuous Current

Primary Fault Interrupting

Secondary Thru-Fault

Interrupting

Interrupting Time

Power Frequency

Short-Time Withstand

Peak Withstand

Short-Circuit Making

Insulator Design

Ambient Temperature

Range

*

4000 A rating is only available thru 145 kV.

40 kA (3 sec), 63 kA (1 sec)

164 kA

63 kA

Porcelain

-40º C to +50º C standard

(-50

o

C to +50

o

C optional)

Ratings

1200 A,1600 A, 2000 A, 3000 A, 4000 A*

25 kA, 31.5 kA, 40 kA

4

3 cycles

60 Hz

Advertising