Title: Southern States

– CSV

Vertical Interrupter Style Circuit Switcher

Product Specification Guide

Page 4 of 9

Publication No.: PSG-806-CSV 06012011


Ratings

Maximum kV Rating

245

Interrupter/Blade BIL (kV)

900

Continuous Current

1200 A

Primary fault Interrupting

20 kA

Secondary Thru-Fault

4 kA

Interrupting Time

6 cycles

Power Frequency

60 Hz

Short-Time Withstand

40 kA (3 sec)

Peak Withstand

104 kA

Short Circuit Making

40 kA

Insulator Design

Porcelain

Ambient Temperature

-30° C to + 50° C

3.02.02 Additional

1. Rated Interrupting Time: 5 cycles for 27 kV through 72.5 kV

units, 3 cycles for 38 kV through
170 kV units, 6 cycles for 245 kV

2. Rated Duty Cycle:

O-0.3 sec-CO-15 sec-CO

3.02.03 Source Supply Voltage

Purchaser will supply the following sources for the motor, auxiliary, and
control circuits:

1. Motor Voltage

48 VDC, 125 VDC, 250 VDC, 120

VAC, or 240 VAC
2. Auxiliary Voltage

120 / 240 VAC, 60 Hz, 1

3. Control Voltage

48 VDC, 125 VDC, 250 VDC, 120

VAC, or 240 VAC

3.03 Interrupter

The circuit switcher shall use SF

6

single gap puffer interrupters. Arc assist type

interrupters are not acceptable. Each interrupter shall be provided with an
overpressure relief device and shall be field refillable. Hermetically sealed
interrupters are not acceptable due to the inherent dangers to purchaser’s
personnel associated with handling fully pressurized SF

6

devices during

installation and also due to potential hazards encountered during transportation
and offloading.

3.04 Insulators

The support insulators and the interrupter insulators shall be ANSI 70 gray in
color and either porcelain or composite in construction.