Space Ray RSCA Series User Manual

Page 11

Advertising
background image

Form #43219000

Sept 2012

10) INSTRUCTIONS FOR PRESSURE TEST GAUGE CONNECTION


Supply Pressure

1. The installer will provide a 1/8" N.P.T. plugged tapping, accessible for test gauge connection immediately

upstream of the gas supply connection to the heater.

Manifold Pressure

1. Turn the gas valve to the "OFF" position. Remove the 1/8" plug from the manifold downstream from the

combination gas valve at one of the outlet pressure taps and connect a 1/8" nipple to the tapped hole.
Connect the gauge to the nipple. Turn on the gas supply.

2. With the main burner operating, check the burner manifold pressure using a water manometer. Gauges

that measure pressure in pounds per square inch are not accurate enough to measure or set the
manifold pressure. All measurements MUST BE made when this heater and all other gas burning
equipment that is connected to the gas supply system are operating at maximum capacity.

3. The combination gas valve is factory set and should not require adjustment. If full rate adjustment is

required, remove the cover screw. Using a small screwdriver, turn the adjustment screw clockwise

to

increase or counterclockwise

to decrease the gas pressure to the burner. Replace the cover screw.

The gas pressures are shown in the following table:

GAS PRESSURE TABLE

Model

Gas Type

Manifold Pressure

Supply Pressure

Minimum

Maximum

RSCA3

Natural Gas

3.5” W.C.

4.5” W.C.

14.0” W.C.

Propane Gas

10.0” W.C.

11.0” W.C.

14.0” W.C.

RSCA6 and
RSCA10

Natural Gas

6.0” W.C.

7.0” W.C.

14.0” W.C.

Propane Gas

10.0” W.C.

11.0” W.C.

14.0” W.C.

Minimum permissible gas supply pressure for purpose of input adjustment.



10

Advertising