13) LIGHTING AND SHUTDOWN INSTRUCTIONS


STANDING PILOT IGNITION SYSTEM (Ignition Suffix “1”)
1)

Turn the dial to “PILOT.” Press the dial in and light the pilot. Hold for 60 seconds and release.

2)

Turn the dial counterclockwise

to “ON.” Use this position for thermostat control. Set the thermostat

for desired room temperature.

3)

If the heater does not light, shut off the gas completely for 5 minutes before attempting to relight.

4)

To shut down the heater, turn the dial clockwise

to “PILOT.” Depress the dial slightly and turn to

“OFF.”

DIRECT SPARK IGNITION SYSTEM (Ignition Suffix “5”)
1)

Turn on gas supply.

2)

Set thermostat to call for heat.


3)

Ignition should occur immediately.

4)

If the burner fails to light, or flame is not detected during the trial for ignition (a period of
approximately 21 seconds), the gas valve is de-energized and the control goes into safety lockout. Turn
thermostat (or power) off for 60 seconds to take out of lockout.

5)

If heater does not light, shut off gas completely for 5 minutes before attempting to relight.

6)

CAUTION: Heater must be grounded. Poor grounding will give nuisance lockouts, particularly during
momentary power interruptions.

7)

To shut down the heater, turn off the gas and the electrical supply.

NOTE: The lighting and shutdown instructions are also shown on the permanent nameplate attached to
the heater.