13039 Probe Conditioning System

INSTALLATION

The compact JIC box is provided with flanges, each having two 1/4" mounting holes. Locate the
box within about 6 feet of the sensor, if possible. Avoid locations close to a source of
combustibles such as the vent pipe of an oil quench tank, or a natural gas fitting that could
develop a leak. Because the reference air pump aspirates air from its immediate vicinity to pump
to the probe reference air fitting, it is possible to experience a significant error in measurement
due to reaction of the combustible with air inside the probe. The result is a low reading of carbon
potential, which will cause the controls to add excess natural gas and overcarburize your work
piece.

OPERATION

Once you have conducted the brief startup procedure outlined here, you need only sit back and
enjoy safe, effective probe conditioning. No special programs to write, no scheduled operator
routines.

With the system wired as illustrated in Fig. 1, the furnace at normal operating temperature, and
the valve on the burnoff air flow meter closed, a burnoff at the AC20 is initiated. Set the burnoff
flow to about 5cfh. Observe the probe temperature and O2 millivolt reading, and adjust the
burnoff airflow until the millivolt reading is below 200 millivolts, preferably at 0. The
temperature will pass through a maximum as the flow is increased, then drop to a value close to
the normal probe temperature. Burnoff will now occur each time the inner door is opened, and
then closed. A manual burnoff can be conducted at any time from the AC20.

Refer to your GOLD PROBETM instruction manual for a complete description of probe
conditioning theory. System operation is described on Fig. 1.

THANK YOU

We think you will be delighted with the performance of your probes once you have installed this
engineered conditioning system. If you have any questions, suggestions or problems, your

GOLD PROBETM team is only as far as your phone. We listen. And we respond. Call 1-800-
666-4330.