KSR-SK-DB In-Line Splice Kit

Tools Required . . .

The following installation procedures are suggested guidelines for
the installation of in-line cable splices. They are not intended to
preclude the use of other methods and good engineering or field
construction practices.

Receiving, Storing and Handling . . .
1. Inspect materials for damage incurred during shipping.
. Report damages to the carrier for settlement.
3. Identify parts against the packing list to ensure the proper

type and quantity has been received.

4. Store in a dry location.

Installation Precautions . . .
• To minimize the potential for arcing and fire caused by product

damage or improper installation use ground-fault protection. The

National Electrical Code (NEC) and Canadian Electrical Code (CEC)

require ground-fault protection of equipment for each branch

circuit supplying electric heat tracing.

• Installation must comply with Thermon requirements and be in-

stalled in accordance with the NEC, CEC, or any other applicable

national and local codes.

• Power connections and end termination must be located in NEMA 4

or 4X enclosures (Thermon KSR-JB or UL Listed equivalent) located

above moisture line.

• De-energize all power sources before opening enclosure.
• Keep ends of heating cable and kit components dry before and

during installation.

• Do not locate the splice in an expansion joint area, where a bend

occurs in the cable, or within a conduit entering or exiting a slab.

• Do not splice cables that have different catalog numbers and/or

voltage ratings.

• Component approvals and performance rating are based on use

of Thermon specified parts only.

• The kit instructions should be used in conjunction with the

installation instruction for the heating cable and other accessary

items.

KSR-SK-DB

1



Item

Quantity

Description

1

1

Heat Shrink 8mm X 35mm (1.10” X 1.80”)



1

Heat Shrink 0mm X 10mm (.79” X 4.7”)

3 & 4

1

Heat Shrink 10mm X 15mm (.39” X 4.9”)

Cut heat shrink into 3 pieces per step 11

5

1

RTV Tube

6



Small Lug (14-16 AWG)

7

1

Large Lug (10-1AWG)

8



Power Connection Boot

9

1

Mastic Tape 5 mm X 150MM (.98” X 5.91”)

3

Kit Contents . . .

Canadian Standard Association

Certified Snow Melting Equipment

for Applications Having a Type

Designation of B

Underwriters Laboratories Inc.

5N3 De-Icing and Snow Melting

Equipment (KOBQ)

4

5

6

7

8

9