10.

Slide heat shrink 1 8mm x 35mm (1.10” x 1.80”)

then heat shrink  0mm x 10mm (.79” X 4.7”)

onto cable as shown.

12.

Repeat steps 1-8 for second cable to be spliced.

Crimp the small lugs to the second cable.

11.

Cut 10mm X 15mm (.39” X 5”) into 3 pieces : 3 

pieces @ 35mm (1.38”) 4 1 piece @ 55mm (.16”).

Slide heat shrink 3 10mm X 35mm (.39” X 1.38”) over

small lugs on each splice connection boot legs.

KSR-SR-DB

Cable

Boot

Heat Shrink 1

8mm X 35mm

(1.10 X 1.80”)

Heat Shrink 

0mm x 10mm

(.79” X 4.7”)

Ground Braid

Small Lug

Heat Shrink 3

10mm X 35mm

(.39” X 1.38”)

Heat Shrink 1

Heat Shrink 

Heat Shrink 3

Small Lug

Crimped

13.

Center heat shrink 3 over crimped small lugs. Using

heat gun, heat until heat shrinks firmly set.

14.

Cut  pieces of mastic tape about 5mm (1”) long.

Stretch mastic tape to cover the end of each splice

connection boot and cable primary insulation jacket

up to metallic braid.

16.

Crimp large lug on one of the braid as shown. Slide

heat shrink 4 over the braid with large lug.

17.

Crimp large lug to the end of the other braid.

Mastic Tape

Heat Shrink 3

Heat Shrink 

Heat Shrink 1

Heat Shrink 3

Heat Shrink 

Large Lug

Heat Shrink 4

10mm x 55mm

(.39” X .17”)

Heat Shrink 4

15.

Center shrink  over splice connection area. Using

heat gun, heat until heat shrink firmly sets.

18.

Center heat shrink 4 over crimped lug. Using heat

gun, heat until heat shrink firmly sets.

Heat Shrink 

Heat Shrink 4