Wavetronix Click 400 (900 MHz radio) (CLK-400) - User Guide User Manual

Page 91

Advertising
background image

90

CHAPTER 9 CLICK 110

Note

This parameter can also be changed using the front panel menu or Click Supervisor.

As mentioned earlier, the Click 110 device receives serial datagrams from a SmartSensor.

These datagrams can contain many channels of detection data.

Because the Click 110 has four output channels, only four input datagram channels, re-

ceived from the sensor, can be output by each device. (If you need more than four channels,

consider using multiple devices.) As shown in the table below, the outputs are mapped

sequentially—that is, they can only be mapped in numerically ordered groups of four (1–4,

5–8, etc.). If you chose, for example, 17–20, then input 17 would be mapped to output 1,

input 18 would be mapped to output 2, input 19 would be mapped to output 3, and input

20 would be mapped to output 4.

If fewer than four outputs are required, any contact closure output can be disabled. A dis-

abled output will never enter the detection state, and will never indicate a fault condition.

Depending on whether each channel is enabled or disabled, the input mapped to it will also

be enabled or disabled.

S3: Channel Input Map

1

2

3

4

Channel

Off

Software mode

On

Off

Off

Off

1–4

On

Off

Off

On

5–8

On

Off

On

Off

9–12

On

Off

On

On

13–16

On

On

Off

Off

17–20

On

On

Off

On

21–24

On

On

On

Off

25–28

On

On

On

On

29–32

Table 9.4 – DIP Switch Channel Input Map Settings

If switch 1 (S3:1) is on (up), Hardware mode is selected, meaning the inputs can be mapped

using the DIP switches (as shown in Table 9.4 above), and Click Supervisor and the front

panel menu will be able to display the current setting, but not change it. (Dashes in the table

above indicate that the other three switches don’t affect Software mode selection.)

If switch 1 is off (down), Software mode is selected and Click Supervisor and the front panel

menu will be able to both display and change the current setting.

Advertising
This manual is related to the following products:

Click 421 (bluetooth to serial converter) (CLK-421) - User Guide, Click 342 (lean managed ethernet switch) (CLK-342) - User Guide, Click 341 (lean managed ethernet switch) (CLK-341) - User Guide, Click 340 (lean managed ethernet switch) (CLK-340) - User Guide, Click 331 (unmanaged ethernet switch) (CLK-331) - User Guide, Click 330 (unmanaged ethernet switch) (CLK-330) - User Guide, Click 304 (RS-232 to RS-485 converter) (CLK-304) - User Guide, Click 305 (RS-232 to RS-485 converter) (CLK-305) - User Guide, Click 301 (serial to ethernet converter) (CLK-301) - User Guide, Click 100 (16 output contact closure) (CLK-100) - User Guide, Click 104 (4-channel DIN rail contact closure) (CLK-104) - User Guide, Click 110 (4-channel contact closure eurocard) (CLK-110) - User Guide, Click 112 (detector rack card) (CLK-112) - User Guide, Click 114 (detector rack card) (CLK-114) - User Guide, Click 120 (screw terminal relay) (CLK-120) - User Guide, Click 121 (spring cage relay) (CLK-121) - User Guide, Click 200 (surge suppression) (CLK-200) - User Guide, Click 201 (1 amp AC to DC converter) (CLK-201) - User Guide, Click 202 (2 amp AC to DC converter) (CLK-202) - User Guide, Click 203 (UPS and battery) (CLK-203) - User Guide, Click 204 (4 amp AC to DC converter) (CLK-204) - User Guide, Click 210 (AC circuit breaker) (CLK-210) - User Guide, Click 211 (AC outlet) (CLK-211) - User Guide, Click 221 (DC surge protector) (CLK-221) - User Guide, Click 222 (system surge protector) (CLK-222) - User Guide, Click 223 (dual-485 surge protector) (CLK-223) - User Guide, Click 230 (AC surge protector) (CLK-230) - User Guide, Click 250 (wireless surge protector) (CLK-250) - User Guide