AEC TCU Series Open Reservoir Water Temperature Control Units User Manual

Page 43

Advertising
background image

Page 44

Open Resevoir Water Temperature Control Units

6-5 Safety Devices

Make sure that only qualified electricians test safety devices!

Safety devices should be tested for function every six (6) months.
Perform the following procedures for testing:


Motor Overload

Disconnect main power. Open the electrical enclosure and rotate
the manual

TEST

button on the motor overload to the tripped

position. Close the enclosure and reconnect main power. Push the

START

button. The unit should not start and the

Pump Overload

indicator should illuminate.

Press the

RESET

button. The unit is now ready for operation.

HAZARDOUS ELECTRICAL CURRENT PRESENT.

Maintain a safe ground and disconnect the power

supply before servicing the unit.

Make sure a qualified electrician makes electrical

connections; disonnect/lock out electricity using OSHA

20CFR 1910.147 standards when servicing the unit.

Safety Thermostat

Disconnect main power. Open the electrical enclosure and
disconnect the neutral lead on the safety thermostat from the
terminal strip. Protect the stripped lead to prevent short circuits.
Close the enclosure, reconnect main power, and push the

START

button. The heater should not turn on and the

Over Temperature

indicator should illuminate. Disconnect main power before
reconnecting the thermostat lead
.