Configuring temperature thresholds for a card

Step Command

1.

Enter system view.

system-view

2.

Configure temperature

thresholds for a card.

In standalone mode:

temperature-limit slot slot-number { inflow | hotspot | outflow }

sensor-num lowerlimit warninglimit [ alarmlimit ]

In IRF mode:

temperature-limit chassis chassis-number slot slot-number { inflow |

hotspot | outflow } sensor-num lowerlimit warninglimit [ alarmlimit ]

Displaying the temperature information on your switch

Use the display environment command to display the temperature information of the sensors on the cards,

including the current temperature and temperature thresholds.
# Display the temperature information of the cards on the switch.

<Sysname> display environment

In standalone mode:

System temperature information (degree centigrade):

-------------------------------------------------------------------------------

Slot Sensor Temperature LowerLimit WarningLimit AlarmLimit ShutdownLimit

0 inflow 1 27 -10 55 80 N/A

0 outflow 1 32 -10 55 80 N/A

0 hotspot 1 32 -10 55 85 N/A

9 inflow 1 34 -10 55 75 N/A

9 outflow 1 34 -10 55 85 N/A

9 hotspot 1 37 -10 55 80 N/A

10 inflow 1 29 -10 55 80 N/A

10 outflow 1 51 -10 55 95 N/A

In IRF mode:

System temperature information (degree centigrade):

-------------------------------------------------------------------------------

Slot Sensor Temperature LowerLimit WarningLimit AlarmLimit ShutdownLimit

1/0 inflow 1 27 -10 55 80 N/A

1/0 outflow 1 32 -10 55 80 N/A

1/0 hotspot 1 32 -10 55 85 N/A

1/9 inflow 1 34 -10 55 75 N/A

1/9 outflow 1 34 -10 55 85 N/A

1/9 hotspot 1 37 -10 55 80 N/A

1/10 inflow 1 29 -10 55 80 N/A

1/10 outflow 1 51 -10 55 95 N/A