Module dimensions and layout, Sitelink-4, Specification for sitelink-4 – Emerson SiteLink-4 User Manual

Page 2: Liebert, Liebert corporation

Advertising
background image

Specification for SiteLink-4

BATTERY:

Seven-year lithium battery provides a minimum or 10,000 hours or data

retention during power outages.


LISTED:

UL 916 (PAZX), cUL C22.2 No. 205-M1983 (PAZX7), FCC Part 15 – Subpart B

- Class A.


DIAGNOSTIC LED's:

Power:

lights when power is being supplied to the module.

Run:

flashes to indicate a normal condition

Error:

lights when an error is detected

CMnet Transmit:

lights when the SiteLink-4 transmits data over the ARC156 network

CMnet Receive:

lights when the SiteLink-4 receives data from the AERC156 network

Port A Transmit:

lights when the SiteLink-4 transmits data over Port A

Port A Receive:

lights when the SiteLink-4 receives data from Port A

Port B Transmit:

lights when the SiteLink-4 transmits data over Port B

Port B Receive:

lights when the SiteLink-4 receives data from Port B

Unit (IGM Port) Transmit:

lights when the SiteLink-4 transmits data over an IGM port

Unit (IGM Port) Receive:

lights when the SiteLink-4 receives data from an IGM port


MODULE DIMENSIONS AND LAYOUT

11 1/4"

28.58cm

7 1/2"

19.05cm

Power
Switch

Port A
Configuration
Jumpers

Port A

Port B

LEDs

Rotary Address

Switches

Format
Button

Keypad/
Display Port

Access Port

CMnet Baud
Rate Jumper

Gnd and
24VAC
Terminals

1"

2.54cm

CMnet Port

CMnet

Rx

Tx

Open Protocol

Communications

Port B

24Vac, 50-60 Hz

12VA, 0.5A
Use Copper

Conductors Only

Class 2

Power

On

Off

Format

10's

1's

Address

Module

Options

Unit 1

+

-

Unit 2

+

Tx

-

Rx

Unit 3

+

Tx

-

Rx

Unit 4

+

Tx

-

Rx

Access

Port

ARC156K

9600/38.4K

E IA-232
E IA-485

485-4w

485-2w

SiteLink-4

Liebert

Communications

Port A

Run
Error
CMnet receive
CMnet transmit
Port A receive
Port A transmit
Port B receive
Port B transmit
Aux1
Aux2

Management Equipment

TYPE: 003212

E143900

88FO

R

Open Energy

T M

n/c

Auxiliary

Device

Port

Ground

24 Vac

S hield

Net -

Net +

2 wire 4 wire

T x +

n/c

n/c

Net+

Rx +

Rx -

T x -

Net-

E IA-232

Tx

DTR

DCD

Rx

S ignal Ground

To Reduce The

Risk of Fire or

Electrical

Shock,
Do Not

Interconnect

the Outputs of

Different Class

2 Circuits.

Caution

Liebert Corporation

Page 2 of 5 SL-27213 Rev. 4; 7/03

Advertising