Machine parameter list, 2 machine parameter list – HEIDENHAIN TNC 122 Technical Manual User Manual

Page 39

Advertising
background image


38

TNC 122

11 Machine Parameters

4/97

11.2 Machine Parameter List

Machine
Parameter

Function and input

Input value

MP 31

Monitoring of encoder signal amplitude
Input values: 0 to 7
Bit 0 Axis X

+0

inactive

+1

active

Bit 1

Axis Y

+0

inactive

+2

active

Bit 2

Axis Z

+0

inactive

+4

active

MP 40

Displayed axes
Input values: 0 to 7
Bit 0 Axis X

+0

not displayed

+1

displayed

Bit 1

Axis Y

+0

not displayed

+2

displayed

Bit 2

Axis Z

+0

not displayed

+4

displayed

MP70

Analog output bipolar or unipolar
Input values: 0 or 2
0 = bipolar
1 = unipolar (ensure that MP1040 = 0!)
traversing the end position outputs 0 V
2 = unipolar, traversing the end position inverts
the nominal-value voltage

MP80

Analog voltage source for rapid traverse from
the control or from external source
Input values: 0 to 2
0 =

reserved

1 = analog voltage from external source
2 = analog voltage from control

(Position control loop closed)

MP110.0-2

Assignment of encoder inputs to the machine
axes
Input values: 0 to 2
0 = encoder input X1
1 = encoder input X2
2 = encoder input X3

MP210

Counting direction of encoder signals
Input values: 0 to 7
Bit 0

Axis X

+0 = positive
+1 = negative

Bit 1

Axis Y

+0 = positive
+2 = negative

Bit 2

Axis Z

+0 = positive
+4 = negative

MP330.0-2

Grating period
Input values: 4, 10, 20, 40, 100, 200 [µm]