Exide Technologies Industrial Battery Charger S47-0079 User Manual

Page 10

Advertising
background image

10

The 046-0371 control can provide an auto-refresh charge as long as the battery remains

connected to the charger if enabled. If AC power is lost during the wait period, the control resumes from
where it left off after power is restored. During the auto-refresh charge, the amp-hours and charge time
are added to the original charge. The refresh charge consists of 30 minutes at the equalize current. To
change the auto-refresh settings, refer to the programming section.

2.1.8 Viewing Charge Information

Additional charge information is available any time by pressing the INFO button. This information

is retained after the battery is disconnected until the next battery is connected. After 20 seconds the
display returns to the default display of amps and volts per cell. The following information can be viewed:

Parameter DISPLAY

DESCRIPTION

Charger State

XXXXXX

Message describing charger state.

Amps

CHARGER DC AMPS

AA: xxxA

Charger current in amps.

Volts/Cell BATTERY

V/C

VC: x.xxVC

Battery voltage in volts per cell (v/c).

Amp Hours

ACCUMULATED AH

AH: xxxxAH

Amp Hours returned for the current (or last) charge cycle.

Charge Time

CHARGE TIME

TC: xx:xxHM

Charge time for the current (or last) charge cycle in hours and minutes.

Percent Return

% AH RETURNED

PR: xxx%

Percent of Amp Hours returned as a function of battery AH rating.

Voltage BATTERY

VOLTS

VV: xx.xV

Total battery voltage in volts.

End Current

CHARGE END AMPS

EA: xxxA

End current for the last charge cycle (current amps if charging)

End Voltage

CHARGE END VOLTS

EV: x.xxVC

End voltage for the last charge cycle (current voltage if charging)

Software SOFTWARE

VERSION

SW: x.xx

Control software version