Irt/c for ambient >100, C cooling requirements, Air cooling chart – Exergen Transmitter IRt/c.XMTR User Manual

Page 2: Irt/c accessories, Air flow requirements

Advertising
background image

C

O

R

P

O

R

A

T

I

O

N

4 9

4 9

4 9

4 9

4 9

51 Water Street, Watertown, MA 02172 USA
800-422-3006 • 617-923-9900 • Fax 617-923-9911

IRt/c Accessories

Up to 450°F (230°C), air alone can provide sufficient cooling with the Cooling Jacket Kit. As the Air Cooling
Chart illustrates, considerably less air is required to cool an IRt/c with a CJK-1 or CJK-2, than an IRt/c.5. For
this reason, the IRt/c is recommended for hot areas if it is possible to bring the sensor close to the target.

The air cooling chart extends above the recommended 450°F (230°C), and can be used there, but caution is
advised due to the possible effects of hot spots.

If air consumption is of concern, or if ambient temperatures are above 450°F (230°C), water cooling is recom-
mended. A small amount of purge air is also recommended when water cooling (see Tech Note #15).

Air pressure required to cool IRt/c with CJK-1 or
CJK-2 at various ambient temperatures,
compared
to requirement for IRt/c models with built-in
air cooling.

*All other IRt/c’s with built-in air cooling.

To estimate air flow requirements, select the
pressure required from the Air Cooling Chart, and
read air flow above.

IRt/c for Ambient >100

0

C Cooling Requirements

Air Flow Requirements

Air Cooling Chart

Ambient Temperature ( F)

(psig)

1

10

100

0

200

400

600

IRt/c.xxx*

CJK-1 or CJK-2

(kPa)

7

70

700

90

180°C

Chart applies to standard ovens. For
forced convection ovens, multiply air
pressure by 3, or add external sleeve
with insulating stagnant air gap.

Flow (SCFM)

Pressure

(psig)

0.001

0.01

0.1

1

10

100

1000

0.01

0.1

1

10

Advertising