SMA SB 3000-US User Manual

Page 54

Advertising
background image

7  Configuration

SMA America, LLC

54

SB30-40-US-IA-en-34

Installation Manual

The inverter is compatible with grounding systems with a 208 V AC output or a 240 V AC output.

Example: Jumper assignment for 240 V Delta: 120 V Stinger

The example shows the jumper assignment for the connection of 3 inverters to a 240 Delta: 120 V Stinger power
distribution grid. Observe the sequence in which the inverters are connected to the line conductors.