3 connecting functional and operational grounding, Connecting functional and operational grounding – SMA AUTOMATIC SWITCH BOX M-20 User Manual

Page 30

Advertising
background image

5 Electrical Connection

SMA Solar Technology AG

30

AS-BOX-M_L-IA-IEN110320

Installation Guide

5.3 Connecting functional and operational grounding

TN system:
When connecting in a TN system, only connect a functional grounding. This connection activates the
EMC interference elimination measures in the Automatic Switch Box. The functional grounding is not
identical to the protective grounding of the Automatic Switch Box.
TT system:
When connecting in a TT system, connect an operational and a functional grounding. This connection
activates the EMC interference elimination measures in the Automatic Switch Box. By means of the
operational grounding, the neutral conductor of the Sunny Backup is grounded via a resistor. The
operational and the functional grounding are not identical to the protective grounding of the
Automatic Switch Box.
Requirements:

☐ In case of a functional grounding, the cable cross-section for copper cables is 6 mm².
☐ In case of a redundant connection of the operational grounding, the cable cross-section for

each copper cable is ≥ 6 mm².

☐ In case of an ordinary connection of the operational grounding, the cable cross-section for

copper cables is ≥ 10 mm².

Connection terminals "PE" in the Automatic Switch Box

The Automatic Switch Box corresponds to protection class II. The connection terminals "PE" in
the connection area do not serve as a protective grounding of the Automatic Switch Box
enclosure. Via the connection terminals "PE" in the connection area of the Automatic Switch
Box, PE of the individual terminals will only be routed through the Automatic Switch Box and
distributed in the following installation.

Advertising
This manual is related to the following products: