Refer to, Table 4, For details on tb1 terminal – Yaskawa 1000 Series Drive Option - Analog Monitor User Manual

Page 19: Fer to, On p, 5 installation procedure

Advertising
background image

5 Installation Procedure

YASKAWA ELECTRIC TOBP C730600 40E 1000-Series Option AO-A3 Installation Manual

19

Ferrule-Type Terminals

Yaskawa recommends using CRIMPFOX 6 by Phoenix Contact or equivalent

ferrule-type terminals with the specifications listed in

Table 5

for wiring to ensure

proper connections.

Note: Properly trim wire ends so loose wire ends do not extend from the crimp terminals.

Table 3 Ferrule-Type Terminal Sizes

Terminal Functions

Table 4 Option Terminal Functions

Ferrule-Type

Terminal

Wire Gauge

mm

2

Phoenix Contact

Model

L

mm (in)

d1

mm (in)

d2

mm (in)

0.25 (24 AWG)

AI 0.25 - 6YE

10.5 (13/32)

0.8 (1/32)

2 (5/64)

0.34 (22 AWG)

AI 0.34 - 6TQ

10.5 (13/32)

0.8 (1/32)

2 (5/64)

0.5 (20 AWG)

AI 0.5 - 6WH

14 (9/16)

1.1 (3/64)

2.5 (3/32)

Terminal

Function

Signal Level

Description

V1

<1> Set the functions and output levels for terminals V1 and V2 using unit parameters. See the unit Instruction Manual

for directions on setting parameters.

Analog voltage output 1

-10 to 10 V

• Analog voltage output for an external monitoring

device

<1>

Output resolution 11-bit plus sign (1/2048)

• Max. load current 3 mA

V2

Analog voltage output 2

AC

Common

0 V

Common for analog voltage output

FE

Ground

Used for grounding shielded lines

d1

d2

6 mm

L