Resetting the CM092 EtherNet/IP Option to the default address (if needed).
„

The factory default settings are as follows:
Configure Network Parameters: USER
IP Address:

192.168.1.20

Subnet: 255.255.255.0
Gateway: 192.168.1.1
Gateway Usage:

Disabled

Symptom: The Yaskawa CM092 EtherNet/IP Option Main web page does not display on the PC
web browser screen.
Corrective Action: Check that the PC is setup and properly connected.
„

If the web page is not visible, check that the PC has been setup and connected properly. If the
PC has been setup and connected properly and the web page is still not visible, the IP address
of the CM092 EtherNet/IP Option may need to be reset to its factory default as follows:

„

Remove power from the drive and wait for the charge lamp to be completely
extinguished. Wait at least five additional minutes for the drive to be completely
discharged. Measure the DC bus voltage and verify that it is at a safe level.

„

Place an jumper between test points C and /LD on the CM092 EtherNet/IP Option as shown in the figure to the right.

„

Reapply power to the drive and wait approximately 10 seconds for the power-up cycle to complete.

„

Remove power from the drive and remove the jumper between C and /LD on the CM092 EtherNet/IP Option.

„

Reapply power to the drive and wait approximately 10 seconds for the power-up cycle to complete. You should now be able to connect to IP address 192.168.1.20
and open the main web page.

WARNING!

Dangerous voltages in excess of 400VDC (230V drives) or 800VDC
(460V drives) are present at the DC bus terminals of the drive.


IP address:

192.168.1.19

Subnet mask: 255.255.255.0