Main Menu: Auto-Tuning <ENTER>

Adaptation to most motors manufactured worldwide is possible with the VS-616G5 automatic tuning
function. Available in both open loop vector and flux vector control modes, the inverter prompts the
user for minimal motor information, then guides the user through a quick, simple tuning process.
Below is the motor data required for automatic tuning in the quick-start mode:

Be sure to uncouple the motor before beginning auto-tuning. After scrolling through tuning parameters
using

∧ key, depress Run key to begin auto-tuning. During tuning, “Tune Proceeding” flashes on the

digital operator display. After complete, “Tune Successful” is displayed.

Note: If the Stop key is depressed during tuning, auto-tuning is interrupted and the motor coasts to

stop. The data changed during tuning returns to its original values.

After tuning is complete, depress the Menu key to exit the auto-tuning mode.

Name

Description

V/f

Control

V/f

w/ PG

Open Loop

Vector

Flux

Vector

Motor Rated Voltage

Sets motor’s rated voltage in VAC.

Motor Rated Current

Sets motor’s rated current in A.

Motor Rated Frequency

Sets motor’s rated frequency in Hz.

Motor Rated Speed

Sets motor’s rated speed in rpm.

Number of Motor Poles

Sets the number of motor poles.

Motor Selection

Chooses connected motor as 1st or 2nd motor.

Chapter 3 - Quick-Start Programming

Auto-Tuning Menu