Yaskawa VS-616G5 Series Revision F Quick-Start User Manual

Page 97

Advertising
background image

94

VS-616G5 Installation & Quick-Start Manual

Gr

oup F

O

pti

on

s *

Func

tion

F3 D

I-0

8, 16 Setu

p

F3-01

Digital Input
Selection
(DI Input)

0~7

1

0

0: (BCD 1%)
1: (BCD 0.1%)
2: (BCD 0.01%)
3: (BCD 1Hz)
4: (BCD 0.1Hz)
5: (BCD 0.01Hz)
6: BCD Special setting 5 digit
input, Binary 255/100%
(BCD (5DG) 0.01Hz)
7: (Binary)*
*Set value is displayed as

decimal.

x

A

A

A

A

Fu

nc

tion

F4 AO-

08. 12

F4-01

Channel 1 Monitor
Selection
(AO Ch1 Select)

1~38

1

2

Analog Output option Channel 1

1: Frequency reference

2: Output frequency

3: Inverter output current

5: Motor speed

6: Output voltage

7: DC bus voltage

8: Output power

9: Torque reference (internal)

15: External terminal 13 input

voltage

16: External terminal 14 input

voltage

17: External terminal 16 input

voltage

18: Motor secondary current (Iq)

19: Motor excitation current (Id)

20: Primary frequency after SFS

21: Speed controller ASR input

22: Speed controller ASR output

23: Speed deviation

24: PID feedback

26: Voltage reference (Vq out-

put)

27: Voltage reference (Vd out

put)

32: ACR (q) Output

33: ACR (d) Output

36: PID Input

<1110>

37: PID Output

<1110>

38: PID Reference

<1110>

x

A

A

A

A

F4-02

Channel 1 Gain
(AO Ch1 Gain)

0.00~

2.50

0.01

1.00

o

A

A

A

A

F4-03

Channel 2 Monitor
Selection
(AO Ch2 Select)

1~38

1

3

Analog Output option Channel 2

selection

(same as F4-01)

x

A

A

A

A

F4-04

Channel 2 Gain
(AO Ch2 Gain)

0.00~

2.50

0.01

0.50

o

A

A

A

A

F4-05

<1110>

CH1 Output Bias
(AO Ch1 Bias)

–10.0
~10.0

0, 1

0.0

o

A

A

A

A

F4-06

<1110>

CH2 Output Bias

–10.0
~10.0

0, 1

0.0

o

A

A

A

A

* When access level is BASIC (A1-03), constant is not displayed unless the option is connected.

Function

Parameter

No.

Name

(Digital Operator

Display)

Setting

Range

Setting

Unit

Factory

Setting

Remarks

(Digital Operator Display)

Change

during

Operation

o: Enabled

x: Disabled

Parameter Access Level

User

Setting

V/f

V/f

w/

PG

Open

Loop

Vector

Flux

Vector

Appendix

VS-616G5 Parameters

Advertising