Network configuration restrictions, Eds files, 5 installation procedure – Yaskawa AC Drive V1000-Series Option SI-M3/V CompoNet User Manual

Page 27: When using round cable i, When using round cable ii and flat cable i/ii

Advertising
background image

5 Installation Procedure

YASKAWA ELECTRIC TOBP C730600 54A V1000 Option CompoNet Installation Manual

27

Network Configuration Restrictions

Some restrictions apply to CompoNet network configuration and vary in accordance with

the type of cable being used.
Refer to the ODVA website at www.odva.org for more information.

When Using Round Cable I

Table 7 Wiring Length when Using Round Cable I

When Using Round Cable II and Flat Cable I/II

Table 8 Wiring Length when Using Round Cable II and Flat Cable I/II

Termination Resistor Connection

Install a termination resistor when connecting the option to the end of a trunk or sub-trunk

line (121

Ω, ±1%, 1/4W).

EDS Files

For easy network implementation of drives equipped with the SI-M3/V option, an EDS file

can be obtained from:
U.S.: http://www.yaskawa.com
Other areas: Contact a Yaskawa representative.

Communication

Speed

Max.

Length of

Trunk Line

Max. Length

of Branch

Line

Total Length

of Branch

Lines

Max. No. of

Slaves per

Branch Line

Max. Length

of Sub-

branch Line

Total Length

of Sub-

branch Lines

4 Mbps

30 m

0 m

0 m

0

0 m

0 m

3 Mbps

30 m

0.5 m

8 m

1

0 m

0 m

1.5 Mbps

100 m

0 m

0 m

0

0 m

0 m

30 m

2.5 m

25 m

3

0 m

0 m

93.75 kbps

500 m

6 m

120 m

1

0 m

0 m

Communication

Speed

Max.

Length of

Trunk Line

Max. Length

of Branch

Line

Total Length

of Branch

Lines

Max. No. of

Slaves per

Branch Line

Max. Length

of Sub-

branch Line

Total Length

of Sub-

branch Lines

4 Mbps

30 m

0 m

0 m

0

0 m

0 m

3 Mbps

30 m

0.5 m

8 m

1

0 m

0 m

1.5 Mbps

30 m

2.5 m

25 m

3

0.1 m

2 m

93.75 kbps

200 m

If total wiring length is 200 m or shorter, no limits apply.