30

YASKAWA ELECTRIC TOBP C730600 54A V1000 Option CompoNet Installation Manual

<1> To start and stop the drive with the CompoNet master device using serial communications, set b1-02 to 3 or set the

“Net Control” bit in the assemblies or Control Supervisor Object. To control the frequency reference of the drive

via the master device, set b1-01 to 3 or set the “Net Reference” bit in the assemblies or AC/DC object.

<2> Setting F6-01 or F6-03 to 3 will allow the drive to continue to operate after detecting a fault. When allowing the

drive to continue operation after fault detection, be sure to take proper safety measures such as installing an

emergency stop switch.

<3> All MAC addresses must be unique.

<4> Unavailable values will initialize Polled Consuming Assembly (PCA) and Polled Producing Assembly (PPA).