5.1 iQpump Basic Programming Parameters

94

YASKAWA TM.iQp.01 iQpump Drive User Manual

drive. When the Forward/Reverse input is open the iQpump drive will run in the Forward direction and when the input is closed, the

iQpump drive will run in the Reverse direction.

In 3-wire operation a momentary closure (> 50 mS) of S1 will cause the iQpump drive to run provided that S2 is held closed. The

iQpump drive will stop anytime the S2-SN connection is broken. If the 3-wire configuration is implemented via a 3-wire Initialization

(A1-03 = “3330: 3-Wire Initial”), then terminal S5 becomes the Forward/Reverse input.

Note: Reverse operation is disabled in the iQpump drive; however, in 3-wire control, one of the multi-function digital inputs

needs to be programmed to 0. Otherwise, the 3-wire control will not work.

Figure 5.8 3-Wire Control

To issue a Run command via serial communication: Set b1-02 = “2: Serial Com” and connect the RS-485/422 serial communication
cable to R+, R-, S+, and S- on the removable terminal block.

To issue the Run command via the network option card: Set b1-02= “3: Option PCB”, and plug a network option board (p/n SI/J) into

the 2CN port on the Control PCB. Consult the manual supplied with the option board for instructions on integrating the iQpump drive
into your network System.

Important: If b1-01= “3: Option PCB” but a network card is not installed in 2CN, an “OPE05” operator programming error will be

displayed on the digital operator and the iQpump drive will not run.

b1-03 Stopping Method

There are four methods of stopping the iQpump drive when the Run command is removed.

0: Ramp to stop: When the Run command is removed, the iQpump drive will decelerate the motor to 0 rpm. The rate of deceleration is
determined by the active deceleration time. The factory default Decel Time is in parameter C1-02.

When the output frequency has dropped below the DC Injection Start Frequency in b2-01 (Default = 0.5 Hz) DC current will be injected

in the motor at a level determined by b2-02 (50% Default). The DC Injection condition will occur for the time specified by b2-04 (0.0
Default), to establish the end point of the ramp. DC injection can be used to insure the motor is at zero rpm prior to the iQpump drive

shutting off.

Setting

Description

0

Ramp to Stop (factory default)

1

Coast to Stop

2

DC Injection to Stop

3

Coast w/Timer

Stop switch
(NC contact)

Operation switch
(NO contact)

Run command
(run on momentary close)
Stop command
(stop on momentary open)

Sequence input common

SN