Diagnostics 3-10

‹

Network Termination

Determine the topology of the network. In a BUS topology, there is a definite beginning and end to the network. In a Free topology only the

either the beginning of end of the network can be determined. Refer to the diagrams below for examples of BUS and Free topologies.

Network termination consists of a resistor and two capacitors as shown in the figure below. Note the polarity of the capacitors. Refer to the “FT

3120/FT3150 Smart Transceiver Data Book” for more information on network termination. It be downloaded from www.echelon.com.






Figure 3.5 – L

ON

W

ORKS

NetworkTermination

„

BUS topology

BUS topology requires termination resistors at the beginning and end of the network.

Table 3.5 – BUS Topology Terminator Device Values

Device

Description

R

105

Ω, 1%, ⅛W

C1 and C2

100

μF, ≥50V (typically aluminum-electrolytic)








Figure 3.6 – L

ON

W

ORKS

BUS Network Topology

„

Free topology

Free topology network requires only one terminator.

Table 3.6 - Free Topology Terminator Device Values

Device

Description

R

52.3

Ω, 1%, ⅛W

C1 and C2

100

μF, ≥50V (typically aluminum-electrolytic)










Figure 3.7 – L

ON

W

ORKS

Free Network Topology