Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 255

Advertising
background image

HOA Keypad Display

Minor Fault Name

FbL

PID Feedback Loss
The PID feedback input is lower than the level set to b5-13 for longer than the time set to b5-14, and

b5-12 is set to 1 or 4.

Cause

Possible Solutions

Parameter settings for b5-13 and b5-14 are

incorrect

Check parameters b5-13 and b5-14.

PID feedback wiring is faulty

Correct the wiring.

Feedback sensor has malfunctioned

Check the sensor and replace it if damaged.

Feedback input circuit is damaged

Replace either the control board or the entire drive. For instructions on replacing the control board,

contact Yaskawa or your nearest sales representative.

HOA Keypad Display

Minor Fault Name

Fdv

Power Supply Frequency Fault
The input power supply frequency exceeded the allowable frequency fluctuation.

Cause

Possible Solution

A momentary power loss occurred.

Reset the fault.

An input power supply wiring terminal is loose.

Check for loose terminals.

The fluctuation in the voltage of the input power

supply is too large.

Increase the Power Supply Frequency Fault Detection Width (L2-27).

The built-in fuse is open.

Replace either the control board or the entire drive. For instructions on replacing the control board,

contact Yaskawa or your nearest sales representative.

The phase rotation direction has changed in the

input power supply.

Correct the wiring.

The detected power supply frequency exceeded the

allowable value.

Improve the power supply.

HOA Keypad Display

Minor Fault Name

HCA

Current Alarm
Drive current exceeded overcurrent warning level (150% of the rated current).

Cause

Possible Solutions

Load is too heavy

Reduce the load for applications with repetitive operations (i.e., stops and starts), or replace the drive.

Acceleration and deceleration times are too short

• Calculate the torque required during acceleration and for the inertia moment.
• If the torque level is not right for the load, take the following steps:
• Increase the acceleration and deceleration times (C1-01 and C1-02).
• Increase the capacity of the drive.

A special-purpose motor is being used, or the drive

is attempting to run a motor greater than the

maximum allowable capacity

• Check the motor capacity.
• Use a motor appropriate for the drive. Ensure the motor is within the allowable capacity range.

The current level increased due to Speed Search

after a momentary power loss or while attempting

to perform a fault restart

The alarm will only appear briefly. There is no need to take action to prevent the alarm from occurring

in such instances.

HOA Keypad Display

Minor Fault Name

inTLK

Interlock Open
ALM LED will not blink

Cause

Possible Solutions

BAS Interlock multi-function input is open

Check the cause of interlock.

HOA Keypad Display

Minor Fault Name

LT-1

Cooling Fan Maintenance Time
The cooling fan has reached its expected maintenance period and may need to be replaced.

Note:

An alarm output (H2-oo = 10) will only be triggered if both (H2-oo = 2F

and H2-oo = 10) are set.

Cause

Possible Solutions

The cooling fan has reached 90% of its expected

performance life

Replace the cooling fan and set o4-03 to 0 to reset the Maintenance Monitor.

6.5 Alarm Detection

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual

255

6

Diagnostics & Troubleshooting