Z3: bypass control communication – Yaskawa Z1000U HVAC Matrix Bypass User Manual

Page 354

Advertising
background image

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

Z2-16

(8572) Digital Input 8 Invert

Select

DI-8 Invert

0: Normal

1: Inverted

0: Normal. Lack of input signal = OFF

1: Inverted. Lack of input signal = ON

Default: 0

Range: 0, 1

218

Z2-23

(8579) Digital Output 7

Function Select

DO-7 Func Sel

Digital Output Function Select

0: Serial Comm Controlled

1: K1 Drive Input Contactor

2: K2 Drive Output Contactor

3: K3 Bypass Contactor

4: K4 Motor 1 Select

5: K5 Motor 2 Select

6: READY (Drive and Bypass)

7: RUN Active (Drive or Bypass)

8: Drive RUN Active

9: Bypass RUN Active

10: HAND Mode Active

11: OFF Mode Active

12: AUTO Mode Active

13: Drive Mode Selected

14: Bypass Mode Selected

15: Drive or Bypass Fault Active

16: Drive Fault Active

17: Bypass Fault Active

18: Auto Transfer Active

19: Serial RUN Command Active

20: Damper Actuator Output

21: ON Always

22: Loss of Load Detected

23: Run Verify

99: Not Used

Default: 7

Range: 0 to 23;

99

219

Z2-24

(857A) Digital Output 8

Function Select

DO-8 Func Sel

Default: 10

Range: 0 to 23;

99

219

Z2-25

(857B) Digital Output 9

Function Select

DO-9 Func Sel

Default: 12

Range: 0 to 23;

99

219

Z2-26

(857C) Digital Output 10

Function Select

DO-10 Func Sel

Default: 15

Range: 0 to 23;

99

219

Z2-31

(8581)

Safety Open Message

Selection

Safety Msg Sel

0: Safety Open

1: Fire Stat

2: Freeze Stat

3: Smoke Alarm

4: Over Pressure

5: Low Suction

6: Vibration Switch

Sets the fault message displayed when an FB01 fault is triggered.

0: Safety Open

1: Fire Stat

2: Freeze Stat

3: Smoke Alarm

4: Over Pressure

5: Low Suction

6: Vibration Switch

Default: 0

Range: 0 to 6

219

u

Z3: Bypass Control Communication

No.

(Addr.

Hex)

Name

LCD Display

Description

Values

Page

Z3-01

(8500) Serial Communications

Protocol Select

Serial Protocol

0: Modbus

1: N2

2: P1

3: BACnet

Selects the bypass serial communications protocol.

0: Modbus

1: N2

2: P1

3: BACnet

Default: 3

Range: 0 to 3

220

Z3-02

(8501) Serial Communications

Node Address Select

Node Address

Selects the bypass serial communications node address.

Default: 1

Min.: 0

Max.: 127

220

Z3-03

(8502) Serial Communications

Baud Rate Select

Baud Rate

0: 1200

1: 2400

2: 4800

3: 9600

4: 19200

5: 38400

6: 57600

7: 76800

8: 115200

Selects the bypass serial communications speed.

0: 1200 bps

1: 2400 bps

2: 4800 bps

3: 9600 bps

4: 19200 bps

5: 38400 bps

6: 57600 bps

7: 76800 bps

8: 115200 bps

Default: 3

Range: 0 to 8

221

Z3-04

(8503) Serial Communications

Parity Select

Parity

0: No Parity

1: Even Parity

2: Odd Parity

Selects the bypass serial communications parity.

0: No Parity

1: Even Parity

2: Odd Parity

Default: 0

Range: 0 to 2

221

B.15 Z: Bypass Parameters

354

YASKAWA SIEP YAIZ1D 01A Z1000U HVAC MATRIX Drive Bypass Technical Manual