Custom End Setting Mode (CST ENd):

The Custom End Setting Mode allows the user to set any specific point as the end position. For example, the end

point may be set at 11mA.

*The difference, between the zero and end points must be greater or equal to 4mA.

Interpolation Mode (ITP OFF/ON):

The positioner can accurately control the valve if the feedback lever angle range is within the designed range. In

some instances, if the angle exceeds the suggested range angle, Interpolation Mode can reduce the error.