Jordan Valve Mark 17X Series Flameproof Smart Positioner User Manual

Page 26

Advertising
background image

-25-

e

rror

and

w

arnIng

C

odes

Error code

Code Description and Cause

Action

MT ERR L

- Positioner is improperly installed

- Positioner is not level to the ground at 50% point.

Lever is at lower position than actual 50% point

- Reinstall the positioner

- Ensure the feedback lever does not

touch the stopper at 0% and 100%

MT ERR H

- Positioner improperly installed

- Positioner is not level to the ground at 50% point.

Lever is at higher position than actual 50% point

- Reinstall the positioner

- Ensure the feedback lever does not

touch the stopper at 0% and 100%

CHK AIR

Valve does not operate when the positioner receives

“Full Open” signal during Auto Cal

- Check supply pressure levels

RNG ERR

Operating angle is too small due to improper

positioner installation

Adjust the mounting bracket so the

positioner can be mounted closer to

the actuator

C

Error of 10% or more persists for more than 1 minute

- No valve movement

- High level of valve friction

- Changes in setting pressure of actuator

- Perform BIAS calibration

- Check setting pressure of actuator

D

I value reaches a maximum or minimum limit

- Changes in valve friction

- Changes in setting pressure of actuator

- Perform Auto Cal

- Check setting pressure of actuator

B

- Pv Span – Pv Zero range is below 500

- The angle of the feedback lever is too small

- Reinstall the positioner

- Ensure the feedback lever does not

touch the stopper at 0% and 100%

- After reinstallation perform AUTO1

F

- Full Open/Close elapsed time is less than one

second

- Actuator size is too small

- Use variable orifice

- Use larger actuator

G

- Pv is below 100

- The angle of the feedback lever is too large

- Reinstall the positioner

- Ensure the feedback lever does not

touch the stopper at 0% and 100%

- After reinstallation perform AUTO1

H

- Pv is over 4000

- The angle if the feedback is too large

- Reinstall the positioner

- Ensure the feedback lever does not

touch the stopper at 0% and 100%

- After reinstallation perform AUTO1

M

ark

17X S

erieS

F

laMeprooF

S

Mart

p

oSitionerS

Advertising