Magnum Energy DC Breakers (BR-DC) User Manual

Magnum Energy Equipment

Advertising
background image

High Capacity DC Breakers Instruction Sheet

Part Number: 64-0040 Rev B

1

Magnum Energy, Inc.

2211 West Casino Rd.

Everett, WA 98204

www.magnumenergy.com

Figure 1, Physical Dimensions

7.

12

5

(180

.9

7)

8.

334

(21

1.

68)

3.

82

8

(9

7.

23)

2.968

(75.39)

1.5

(38.1)

Introduction

The BR-DC175 and BR-DC250 are the same DC breakers installed in the MP

(Magnum Panel) and MMP (Mini Magnum Panel) system enclosures, and in-

cluded with the MPX extensions. These breakers function as the inverter’s DC

disconnect switch and can be used as the battery-to-inverter circuit protection

in most installations. These breakers were specifi cally designed and tested to

work with Magnum inverters to provide the delay time needed to minimize

nuisance breaker tripping.
Depending on the part number, the circuit breaker is either a 175 amp (PN:

BR-DC175) or a 250 amp (PN: BR-DC250), high interruption capacity, mag-

netic-hydraulic, DC circuit breaker. These breakers have front-accessible con-

nections, each provided with a 3/8-16 captive nut. Each breaker includes two

3/8-16 Hex head bolts with washers, and a back mount kit for installing this

breaker inside MP enclosures. This kit consists of two mounting straps and two

#10-32 x 3.5” Torx screws to attach the DC breaker to a mounting panel.

CAUTION: These breakers must be mounted in a vertical position

to meet the specifi ed trip current and trip delay curve.

Specifi cations

Approvals

UL 489 Listed Branch Circuit-Breaker

CSA Certifi ed C22.2 No. 5

Interrupting Capacity

10,000 amperes at 160VDC

65,000 amperes at 65VDC


Trip Time Delay

Customized Delay 53 (DC long delay),

constructed to work specifi cally with

Magnum inverters.
Recommended Torque:

220 - 230 inch-pounds (using 3/8”

bolts to connect cables - having ring

lug terminals - to the 3/8-16 captive

nuts on the copper extensions).
Physical:

Weight: ~2.25 lbs. (1020 grams)

Size: See Figure 1

Terminal connections: Two Front-

accessible, tinned-copper extensions,

each with a 3/8-16 x 1” bolt and

washer screwed into a captive nut.

Sizes shown in

inches (mm)

Advertising