Optional rack-mounting equipment, Mounting, Rack mounting – Enterasys Networks VSER-RPU-SYS User Manual

Page 17: Mounting 2-3

Advertising
background image

Mounting

2-3

2

The device history (i.e., have you returned the device before, is this a recurring
problem, etc.)

Any previous Return Material Authorization (RMA) numbers

Optional Rack-Mounting Equipment

If you plan to rack-mount the RPS, be sure to have the following equipment
available:

• Four mounting screws for each device you plan to install in a rack—these are not

included

• A screwdriver (Phillips or flathead, depending on the type of screws used)

Mounting

RPS units can be mounted in a standard 19-inch equipment rack or on a desktop or
shelf. Mounting instructions for each type of site follow.

Rack Mounting

Before rack mounting the unit, pay particular attention to the following factors:

• Temperature: Since the temperature within a rack assembly may be higher than

the ambient room temperature, check that the rack-environment temperature is
within the specified operating temperature range.

• Mechanical Loading: Do not place any equipment on top of a rack-mounted unit.
• Circuit Overloading: Be sure that the supply circuit to the rack assembly is not

overloaded.

• Grounding: Rack-mounted equipment should be properly grounded. Particular

attention should be given to supply connections other than direct connections to
the mains.