Mounting and wiring, Multi-stage terminal outputs, Heat pump terminal outputs – Emerson 1F73 User Manual

Page 4

Advertising
background image

MOUNTING AND WIRING

CONTINUED FROM PAGE 3

4

C*

R

O/B/Y2*

Compressor

Contactor

Stage 1

Heat

Relay

Stage 1

Heat

Relay

Stage 2

24 VAC

120 VAC

Hot

Neutral

THERMOSTAT

SYSTEM

Y1

E/W1

W2

Figure 5. Typical wiring diagram for single transformer multi-stage systems

Fan

Relay

G

TRANSFORMER

(Class II, Current Limited)

*O/B Switch must be in “O” position

Compressor

Contactor

Stage 2

Refer to equipment manufacturers’ instructions for specific sys-
tem wiring information.

You can configure the thermostat for use with either multi-stage
electric heat systems or multi-stage gas systems. When config-
ured for electric heat, the G terminal (blower/fan) will be ener-
gized on a call for heat.

This thermostat is designed to operate a single-transformer
system. If you have a two-transformer system, cut and tape of one

transformer. If transformer safety circuits are in only one of the
systems, remove the transformer of the system with NO safety
circuits. If required, replace remaining transformer with a 75VA
Class II transformer. After disconnecting one transformer, the two
commons must be jumpered together.

Use the terminal output information below to help you wire the
thermostat properly for your multi-stage system. After wiring, see
CONFIGURATION section for proper thermostat configuration.

Multi-stage Terminal Outputs

Refer to equipment manufacturers’ instructions for specific sys-
tem wiring informtion.

You can configure the thermostat for use with the following heat
pump system types:

HEAT PUMP TYPE 1. Single-stage compressor system; gas or
electric backup.

This thermostat is designed to operate a single-transformer
system. If you have a two-transformer system, cut and tape of one

Heat Pump Terminal Outputs

transformer. If transformer safety circuits are in only one of the
systems, remove the transformer of the system with NO safety
circuits. If required, replace remaining transformer with a 75VA
Class II transformer. After disconnecting one transformer, the two
commons must be jumpered together.

Use the terminal output information below to help you wire the
thermostat properly for your multi-stage system. After wiring, see
CONFIGURATION section for proper thermostat configuration.

SYSTEM

L

C

R

W2

E/W1

(O/B)Y2*

Y1

G

Malfunction

Light

Multi-Stage

*O/B switch must be in “O” position

24 Volt

(Common)

24 Volt

(Hot)

Heat mode

2nd stage

Heat mode

1st stage

Cool Mode

2nd stage

Cool mode

1st stage

Blower/Fan Energized

on call for Cool (and

Heat if configured

to Electric Heat)

THERMOSTAT TERMINALS

SYSTEM L C

R W2 E/W1 (O/B)Y2 Y1 G

Single-stage compressor system; gas or electric backup

Malfunction

Light

Heat Pump 1

24 Volt

(Common)

24 Volt

(Hot)

Heat mode

2nd stage

(Aux.)

Emergency

Mode

Heat

B: Energized in Heat, Off,

Emergency Mode

O: Energized in Cool Mode

Heat and

Cool mode

1st stage

(compressor)

Blower/Fan Energized

on call for Heat

and Cool

THERMOSTAT TERMINALS

www.white-rodgers.com