Symptom

Possible Cause

Corrective Action

Furnace/Air Conditioner Cycles Too Fast or

1. The location of the thermostat and/or the

Digital thermostats normally provide precise

Too Slow (narrow or wide temperature swing)

size of the Heating/Cooling System may be

temperature control and may cycle faster than

influencing the cycle rate.

some older mechanical models. A faster cycle
rate means the unit turns on and off more
frequently but runs for a shorter time so there is
no increase in energy use. If you would like to
increase the cycle time, refer to step 3 on the
Configuration Menu

Thermostat Setting and Thermostat

1. Thermostat thermometer setting requires

The thermometer can be adjusted +/- 3 degrees.

Thermometer Disagree

adjustment.

See Temperature Display Adjustment in the

Operation section.

Blank Display and/or Keypad Not

1. Voltage spike or static discharge.

Use the Reset Operation listed above.

Responding

Heat Setpoint Will Not Respond

1. The desired setpoint conflicts with the

Change system mode to COOL. Raise the Cool

to the Temperature Up Key

setpoint of the COOL mode.

setpoint. Return to HEAT mode and set desired
temperature.

Cool Setpoint Will Not Respond

1. The desired setpoint conflicts with the

Change system mode to HEAT. Lower the Heat

to the Temperature Down Key

setpoint of the HEAT mode.

setpoint. Return to COOL mode and set desired
temperature.

TROUBLESHOOTING