7

Temperature Probes:

NTC
The control is shipped with an NTC (Negative Temperature
Coefficient) sensor, with a cable length of 7½ feet. Cable
length can be extended up to 400 feet by appropriately splic-
ing and adding additional cable (22 AWG or larger diameter)

PTC
The control may be connected to an existing PTC (Positive
Temperature Coefficient) sensor. Make sure the PTC sensor
meets the specifications tables below. Failure to do so will
result in temperature inaccuracies. The PTC input may not be

NTC TEMPERATURE VERSUS RESISTANCE TABLES

PTC TEMPERATURE VERSUS RESISTANCE TABLES

as needed – polarity is not important. When extending cable
length, verify temperature accuracy and use the menu Ambi-
ent Temperature Offset (OFS) settings to compensate accord-
ingly if required.

extended more than 50 feet, and the wire gauge should be
18 AWG wire or larger diameter. Be sure the probe attached
matches the resistance vs. temperature tables or temperature
inaccuracies may occur.

SPECIFICATIONS

Temperature

(°F) (°C)

Resistance

(K

Ω)

-40

-40

328.29

-31

-35

236.83

-22

-30

172.90

-13

-25

127.65

-4

-20

95.23

5

-15

71.74

14

-10

54.56

23

-5

41.85

32

0

32.37

41

5

25.23

Temperature

(°F) (°C)

Resistance

(K

Ω)

50

10

19.82

59

15

15.67

68

20

12.48

77

25

10.00

86

30

8.07

95

35

6.55

104

40

5.34

113

45

4.38

122

50

3.61

131

55

2.99

Temperature

(°F) (°C)

Resistance

(K

Ω)

140

60

2.49

149

65

2.09

158

70

1.76

167

75

1.48

176

80

1.26

185

85

1.07

194

90

0.92

203

95

0.79

212

100

0.68

221

105

0.59

Temperature

(°F) (°C)

Resistance

(K

Ω)

-40

-40

613

-31

-35

640

-22

-30

668

-13

-25

697

-4

-20

727

5

-15

758

14

-10

789

23

-5

822

32

0

855

41

5

889

Temperature

(°F) (°C)

Resistance

(K

Ω)

50

10

924

59

15

960

68

20

997

77

25

1035

86

30

1074

95

35

1113

104

40

1153

113

45

1194

122

50

1236

131

55

1279

Temperature

(°F) (°C)

Resistance

(K

Ω)

140

60

1323

149

65

1368

158

70

1413

167

75

1459

176

80

1506

185

85

1554

194

90

1602

203

95

1652

212

100

1702

221

105

1753

Load Output Relay:

Ratings (Maximum):

120VAC 208VAC 240VAC

Full Load Amps NC & Load

16 A

9.2 A

8 A

Locked Rotor Amps NC & Load

96 A

55.2 A 48 A

Non-Inductive Amps NC & Load

16 A

16 A

16 A

Horsepower NC & Load

1 hp

1 hp

1 hp

24 VAC NC & Load

100 VA, 30 VAC Max (Class 2)

Pilot Duty NC & Load

125 VA, 24 to 240 VAC

• Minimum Load Rating: 1 Amp @ 24 VAC
• Note: the above minimum current/voltage is specified
to assure proper operation.

NOTE: For use on single phase circuits only.

Alarm Relay Ratings (Maximum):
N.O. contact: 1 Amp, 5 to 24 V, AC or DC

Operating Ambient Ratings (Control Enclosure):
Operating Temperature:

-29°F to 140°F (-34° to 60°C)

Storage Shipping Ambient Ratings:
Storage Temperature:

-40°F to 185°F (-40° to 85°C)

Operating Humidity:

0 to 95% Relative Humidity,

Non-Condensing

Maximum Dew Point:

85°F (29°C)

Temperature Set-Point Range:
Set-Point Range: -40° to 220°F (-40° to 104°C)
Differential Range:

1 to 30 (Degrees F or Degrees C)

Case:
NEMA 1 Enclosure, Flammability Rating: UL94VO

Advertising